126 Technical data

Input cable fuses

The ratings of UL listed fuses for branch circuit protection are listed below. The
fuses also prevent damage to the adjoining equipment of the drive in case of a
short-circuit inside the drive. Make sure that the operating time of the fuse is less
than 0.1 seconds. The operating time depends on the supply network impedance
and the cross-sectional area and length of the supply cable. The fuses must be of the
"non-time delay" type. See
Note 1: In multi-cable installations, install only one fuse per phase (not one fuse per conductor).
Note 2: Larger fuses must not be used.
Note 3: Fuses from other manufacturers can be used if they meet the ratings.
ACS800-U31 type
ACS800-31 type
Three-phase supply voltage 208 V, 220 V, 230 V or 240 V
-0011-2
-0016-2
-0020-2
-0025-2
-0030-2
-0040-2
-0050-2
-0060-2
Three-phase supply voltage 380 V, 400 V, 415 V, 440 V, 460 V, 480 V or 500 V
-0020-5
-0025-5
-0030-5
-0040-5
-0050-5
-0060-5
-0070-5
-0100-5
-0120-5
Three-phase supply voltage 525 V, 575 V, 600 V
-0060-7
-0070-7
-0100-7
Thermal overload and short-circuit protection
Input
current
A
A
32
40
600
44
70
600
55
80
600
70
90
600
82
100
600
112
150
600
140
200
600
157
200
600
29
40
600
33
50
600
44
70
600
54
80
600
65
90
600
76
100
600
112
150
600
129
200
600
145
200
600
53
80
600
73
100
600
86
125
600
Fuse
V
Manufacturer
Bussmann
Bussmann
Bussmann
Bussmann
Bussmann
Bussmann
Bussmann
Bussmann
Bussmann
Bussmann
Bussmann
Bussmann
Bussmann
Bussmann
Bussmann
Bussmann
Bussmann
Bussmann
Bussmann
Bussmann
(page 53).
Type
UL class
JJS-40
T
JJS-70
T
JJS-80
T
JJS-90
T
JJS-100
T
JJS-150
T
JJS-200
T
JJS-200
T
JJS-40
T
JJS-50
T
JJS-70
T
JJS-80
T
JJS-90
T
JJS-100
T
JJS-150
T
JJS-200
T
JJS-200
T
JJS-80
T
JJS-100
T
JJS-125
T
00184674