Frame sizes R6: Cable lug installation [16 to 70 mm
PE
6
5
Frame size R6: Screw terminal installation [95 to 210 mm
PE
6
5
2
(6 to 2/0 AWG) cables]
Remove the screw terminals. Fasten the cable
lugs to the remaining bolts with M10 nuts.
Isolate the ends of
the cable lugs with
insulating tape or
shrink tubing.
Shroud on the conductor terminals (screw
terminal installation)
5
9
2
b
a
a.
Connect the cable to the terminal.
b.
Connect the terminal to the drive.
WARNING! If the wire size is less than
5
95 mm
used. A cable of wire size less than
95 mm
terminal can loosen and may damage
the drive.
Electrical installation 75
(3/0 to 400 MCM)] cables
2
(3/0 AWG), a cable lug must be
2
(3/0 AWG) connected to this
9