To control the line-side converter...

Step
Action
1.
Enter the Drive Selection Mode.
Note: In local control mode, the motor-side
converter trips if parameter 30.02 PANEL LOSS is
set to FAULT. Refer to the appropriate control
program firmware manual.
2.
Scroll to ID number 2.
3.
Verify the change to the line-side converter and
display the warning or fault text.
WARNING! The drive does not stop by pressing the control panel Stop key
in local control mode.
Start-up and use 105
Push key
Display (example)
ACS 800 0050_5MR
DRIVE
ASXR7xxx
ID-NUMBER 1
ACS 800 0050_5LR
IXXR7xxx
ID-NUMBER 2
2
-> 380.0 V
ACS 800 0050_5LR
ACT
** FAULT **
DC OVERVOLT
(3210)