86 Installation of the AGPS board (Prevention of unexpected start-up, +Q950)

Start-up and validation

Action
Obey the safety instructions. See
Make sure that the drive can be run and stopped freely during the start-up.
Stop the drive (if running), switch the input power off and isolate the drive from the power
line by a disconnector.
Check the Prevention of unexpected start-up circuit connections against the circuit diagram.
Close the disconnector and switch the power on.
Test the operation of the Prevention of unexpected start-up function when the motor is
stopped:
• Give a stop command for the drive (if running) and wait until the motor shaft is at
standstill.
• Activate the Prevention of unexpected start-up function and give a start command for the
drive.
• Ensure that the drive does not start and the motor stays at standstill.
• Deactivate the Prevention of unexpected start-up function.

Use

Activate the function as follows:
Stop the drive. Use the Stop key on the panel (local mode) or give the stop
command through the I/O or fieldbus interface.
Open the switch activating the Prevention of unexpected start-up function of
the drive. -> The indication lamp (if it is installed) is on.
Lock the switch to the open position.
Before starting the work on the machinery, ensure that the motor shaft is at
standstill (not freely rotating).
Inactivate the function in the reverse order.

Maintenance

After the operation of the circuit is validated at start-up, it does not need any
maintenance. However, it is a good practice to check the operation of the function
when other maintenance routines of the machinery are carried out.

Dimensional drawing

See page 137.
Safety instructions
on page 11.