Symbols; Sizing - ABB ACS800-31 Hardware Manual

Hide thumbs Also See for ACS800-31:
Table of Contents

Advertisement

120 Technical data
ACS800-31
Nominal
type
ratings
I
cont.max
A
-0060-3
120
-0070-3
150
-0100-3
165
Three-phase supply voltage 380 V, 400 V, 415 V, 440 V, 460 V, 480 V or 500 V
-0020-5
31
-0025-5
36
-0030-5
47
-0040-5
58
-0050-5
70
-0060-5
82
-0070-5
120
-0100-5
139
-0120-5
156
Three-phase supply voltage 525 V, 550 V, 575 V, 600 V, 660 V or 690 V
-0060-7
57
-0070-7
79
-0100-7
93

Symbols

Nominal ratings
I
continuous rms output current. No overload capability at 40 °C (104 °F).
cont.max
I
maximum output current. Available for 10 s at start, otherwise as long as allowed by drive
max
temperature.
Typical ratings:
No-overload use
P
typical motor power. The power ratings apply to most IEC 60034 motors at the nominal
cont.max
voltage, 230 V, 400 V, 500 V or 690 V.
Light-overload use (10% overload capability)
I
continuous rms current. 10% overload is allowed for one minute every 5 minutes.
2N
P
typical motor power. The power ratings apply to most IEC 60034 motors at the nominal
N
voltage, 230 V, 400 V, 500 V or 690 V.
Heavy-duty use (50% overload capability)
I
continuous rms current. 50% overload is allowed for one minute every 5 minutes.
2hd
P
typical motor power. The power ratings apply to most IEC 60034 motors at the nominal
hd
voltage, 230 V, 400 V, 500 V or 690 V.

Sizing

The current ratings are the same regardless of the supply voltage within one voltage
range. To achieve the rated motor power given in the table, the rated current of the
drive must be higher than or equal to the rated motor current.
Note 1: The maximum allowed momentary motor shaft power is limited to
approximately 1.3 ·
automatically restricted. The function protects the input bridge and LCL filter of the
drive against overload.
Note 2: The ratings apply at an ambient temperature of 40 °C (104 °F). At lower
temperatures the ratings are higher (except
Note 3: Use the DriveSize PC tool for a more accurate dimensioning if the ambient
temperature is below 40 °C (104 °F) or the drive is loaded cyclically.
Light-overload
No-
overload
use
use
I
I
P
max
cont.max
2N
kW
A
A
168
55
114
234
75
143
264
90
157
52
18.5
29
61
22
34
68
30
45
90
37
55
118
45
67
130
55
78
168
75
114
234
90
132
264
110
148
86
55
54
120
75
75
142
90
88
P
.
If the limit is exceeded, motor torque and current are
cont.max
Heavy-duty use Frame
P
I
P
N
2hd
hd
kW
A
kW
55
88
45
75
117
55
75
132
75
18.5
25
15
22
30
18.5
30
37
22
37
47
30
45
57
37
45
62
37
75
88
55
90
114
75
90
125
75
45
43
37
55
60
55
75
71
55
I
).
max
Air flow Heat dis-
size
sipation
W
3
m
/h
R6
405
1750
R6
405
2350
R6
405
2800
R5
350
655
R5
350
760
R5
350
1000
R5
350
1210
R5
350
1450
R5
350
1750
R6
405
2350
R6
405
2800
R6
405
3400
R6
405
1750
R6
405
2350
R6
405
2800
00184674