Start-up and use

What this chapter contains

This chapter describes the start-up procedure and use of the drive, and the control
panel control of the line-side and motor-side converters.
Start-up and use
WARNING! Only qualified electricians are allowed to commission the drive.
Read and obey the
safety instructions can cause injury or death.
Remove the protective film covering the unit.
Do the start-up procedure as described in the appropriate control program firmware
manual. The parameters of the line-side converter control program need not be set
in a normal start-up procedure or in normal use. However, it is recommended to set
parameter 16.15 START MODE to LEVEL:
if the motor is started and stopped frequently. This prolongs the lifespan of the
charging contactor.
when starting the motor without start delay is required.
if the drive is connected to other drives via a common DC bus. Otherwise, the
charging resistor may be damaged.
For setting of parameter 16.15 START MODE, change the control panel to control the
line-side converter as shown on page 105.
Notes:
By default, the control panel controls the RMIO board of the motor-side
converter (ID number 1). If the control panel is set to control the RMIO board of
Safety instructions
(page 11) in this manual. Ignoring the
Start-up and use 103
11

Advertisement