100 Installation checklist
Check that...
ELECTRICAL INSTALLATION
Planning the electrical installation
See
The +E202 and +E200 EMC filter capacitors are disconnected if the drive is
connected to an IT (ungrounded) system.
IT (ungrounded) systems
See
The capacitors are reformed if stored over one year, refer to
modules with electrolytic DC capacitors in the DC link, Capacitor reforming
instructions
The drive is grounded properly.
The mains (input power) voltage matches the drive nominal input voltage.
The mains (input power) connections at U1, V1 and W1 and their tightening
torques are OK.
Appropriate mains (input power) fuses and disconnector are installed.