D5.2
longer than 3 meters.
It must be installed a "T" with hermetic cover at the stove exit smoke that
allows the regular inspection or the heavy dust download.
Trebol and Mila models have a register "T" included with the stove.
There will not be more than 4 changes of direction, including the register
"T" for the cleaning.
In drawing D5.4 are represented the basic requirements for the chimney
installation of a thermo-stove:
The flue must be away from flammable or combustible materials through an appropriate insulation or an air chamber. Inside the pipes, it is
forbidden the use of air abduction channels. It is also prohibited to do mobile or fixed openings for connecting other different equipments.
The smoke duct must be staunchness set to the equipment and it can have a maximum inclination of 45° whereby excessive deposits of
condensation produced in the initial stages of ignition and / or excessive soot formation is avoided. Moreover, it avoids the slowing down of
the smoke when it comes out.
The lack of sealing of the connection may cause the malfunction of the equipment.
The internal diameter of the connection pipe should correspond to the external diameter of the chimney of the equipment.
In drawing D5.5 you can see the requirements for a correct installation.
INSTALLATION, OPERATING AND SERVICING INSTRUCTIONS
Materials that are prohibited for the chimney and, therefore, damage the proper functioning of the equipment
are: fibre cement, galvanized steel and rough and porous interior surfaces. A example of solution is described
below:
(1) Stainless steel AISI 316 chimney with double insulated chamber and material resistant up to 400°C.
Efficiency 100% optimum (see drawing D5.2).
All stoves that send smoke to the exterior
should have their own chimney. Never use
the same chimney for several equipments
at the same time (see drawing D5.3).
It is not recommended the fit in horizontals
sections. The horizontal section will not be
Minimum height 1.5
D5.3
D5.4
D5.5
28
Minimum height 1.5
TREBOL - MILA - MINERVA