7.2 MDS-C1-Vx High-gain (MDS-B-Vx4 Compatible)
No.
Items
2221
SV021
Overload
OLT
detection
time
constant
2222
SV022
Overload
OLL
detection
level
2223 SV023
Excessive
OD1
error
detection
width during
servo ON
2224 SV024
In-position
INP
detection
width
7. Servo Parameters
Details
Set the detection time constant of Overload 1 (Alarm 50).
Set to "60" as a standard. (For machine tool builder
adjustment.)
Set the current detection level of Overload 1 (Alarm 50) in
respect to the stall (rated) current. Set to "150" as a
standard. (For machine tool builder adjustment.)
Set the excessive error detection width when servo ON.
<Standard setting value>
Rapid traverse rate
(mm/min)
OD1=OD2=
60*PGN1
When "0" is set, the excessive error detection will not be
performed.
Set the in-position detection width.
Set the accuracy required for the machine.
The lower the setting is, the higher the positioning
accuracy gets, however, the cycle time (setting time)
becomes longer. The standard setting is "50".
113
Get other manuals https://www.bkmanuals.com
Setting range
1 to 999
(s)
110 to 500
(Stall [rated]
current %)
0 to 32767
(mm)
/2 (mm)
0 to 32767
(µm)