Programming
3.5.8 Clear Program
PROGRAMMING
1=WALKTEST
2=CLEAR PROGRAM
3=PASSWORD CHANGE
Programming Screen #3
3.5.9 Password Change
PROGRAMMING
1=WALKTEST
2=CLEAR PROGRAM
3=PASSWORD CHANGE
Programming Screen #3
104
The user can now perform a one-person walktest by activating devices throughout the system. As
each device is activated, the screen will display the information about the activated device as shown
below. Note that the colon (:) in the time is replaced with an asterisk (*) to distinguish the walk-
test screen from an actual alarm screen.
ALARM ZONE 1
After completion of the Walktest, press the Esc (Escape) key to exit Walktest Mode and return to
the Walktest Screen. The results of the Walktest can now be viewed by pressing 3 while viewing
the Walktest Screen. The following screen will be displayed:
Use the up and down arrow keys to view all of the walktest results which will be displayed as illus-
trated in the preceding screen. Note that the Walktest log is stored in RAM. If all power (AC and
DC) is removed from the FACP, the Walktest log information will be lost. This information is also
overwritten when subsequent walktests are performed.
Pressing 2 while viewing Programming Screen #3, will select the Clear Program option. The con-
trol panel will provide a warning to the user by prompting with the following display:
1=YES
Pressing 1 will cause the control panel to carry out the selected clear option. Pressing 2 will pre-
vent programming from being cleared.
The factory set passwords, which have been programmed into the control panel, can be changed by
selecting the Password Change option. Pressing 3 while viewing Programming Screen #3 will
cause the following screen to be displayed:
1=MASTER
2=MAINTENANCE
3=REMOTE DOWNLOAD
<ADJ> <NOUN>
10*00A 010805
WALKTEST RESULTS
WARNING!
SYSTEM CHANGE
PROCEED?
PASSWORD CHANGE
Password Change Screen
MS-5UD & MS-10UD Series Manual — P/N 52626:C2 1/24/2012
Master Programming Level
Z01
2=NO