Programming
Select the number of minutes allowed, 1-60, before a fault is shown on the panel.

Primary and Secondary Communication Paths

COMMUNICATOR
1=PRI COMM PATH
2=SEC COMM PATH
3=TBL CALL LIMIT
Communicator Screen #1
POTS
XXX COMM PATH
1=POTS
2=ETHERNET
3=CELLULAR
Comm Path Screen
POTS XXX COMM PATH
1=ENABLED
NO
2=ACCT CODE
000000
POTS (XXX) Path Screen #1
Enable
To enable the phone line, press 1 while viewing the POTS Line (X) Screen #1 to change the display to Enabled Yes. Each press of the 1
key will cause the display to toggle between Enabled Yes and Enabled No.
NOTE: For UL applications: when POTS is used as the primary communication path, the use of POTS as the secondary transmission path
is only allowed with approval of the local AHJ.
For ULC applications: when POTS is used as the primary transmission path, alarm signals will be sent out on both the primary and
secondary transmission paths.
Account Code
POTS XXX COMM PATH
1=ENABLED
2=ACCT CODE
000000
POTS Comm Path Screen #1
The Account Code, which is assigned by a Central Station, depends on the communication format being used. The Account Code screen
will have a flashing cursor in the lower left corner. Enter the supplied account code using 0 - 9 and A- F keys.
Phone Number
POTS XXX COMM PATH
1=PHONE NUMBER
2035554321
POTS Comm Path Screen #2
The Phone Number screen is used to enter the Central Station phone number that the Communicator will be contacting. A maximum of
20 characters can be entered with valid entries being 0 - 9 and A - C where A = *, B = # and C = 2 seconds pause.
A flashing cursor will appear in the lower left corner of the screen. Enter the first digit then press the right arrow key to move the cursor
to the right one position. Enter the second digit and repeat the process until all digits are entered. Press the Enter key to store the phone
number in memory.
84
The Primary and Secondary Communication Path screens are used to configure the methods (primary and
backup) for reporting to central station. Pressing 1 for Pri or 2 for Sec will display the following screens.
Note that the following information must be entered for both the Primary and Secondary Communication
0
Paths.
1=POTS
2=ETHERNET
3=CELLULAR
To configure the communication method to contact central station as a telephone line, select 1 for POTS.
The following screens will display.
POTS XXX COMM PATH
1=PHONE NUMBER
2035554321
POTS (XXX) Path Screen #2
Pressing 3 while viewing POTS (XXX) Path Screen #1 will cause the following screen to be displayed:
NO
ENTER 6 DIGITS

Pressing 2 while viewing POTS XXX Path Screen #2 will cause the following screen to be displayed:
XXX COMM PATH
Comm Path Screen
POTS XXX COMM PATH
1=COMM FORMAT
ADEMCO CONTACT ID
POTS (XXX) Path Screen #3
ACCOUNT CODE
Account Codes Screen
PHONE NUMBER
20 NUMBERS MAXIMUM
Phone Numbers Screen
ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018
Master Programming Level
POTS XXX COMM PATH
1=TEST TIME INT
24
2=24HR TEST TIME 0100
POTS (XXX) Path Screen #4