System Options
9.6.5 Miscellaneous Options
Through this programming option you can turn on or off strobe synchronization during silence, display status at Idle (auto display event),
report by zone or point, and single key ack.
To edit miscellaneous options:
1.
Enter the Installer Code.
2.
Select 7 to access the Program Menu.
3.
Select 5 to access the System Options.
4.
Select 5 to access the Miscellaneous Options.
Strobes Active when Silenced
When "SYNC Strobe:" is selected as Y (Yes), the strobes will continue to flash when the System is silenced and will stop flashing when the
System is reset.
NOTE: The "SYNC Strobe:" only functions with outputs that use a synchronized output pattern.
5.
Press the up or down arrow key to toggle this selection between Y (Yes) or N (No).
6.
Press right arrow key or ENTER to make your selection and move to the next programming option.
Auto Display Events
When this feature is programmed Y (Yes), the highest priority event of the System in control will automatically display on the control panel
and remote annunciators after there has been no activity on any system touch pad for two minutes.
7.
Press the up or down arrow key to toggle this selection between Y (Yes) or N (No).
8.
Press right arrow key or ENTER to make your selection and move to the next programming option.
9.6.6 Daylight Saving Options
To edit Daylight Savings:
NOTE: For UL installations, the Alarm Verification Time cannot be less than 60 seconds.
1.
Enter the Installer Code.
2.
Select 7 to access the Program Menu.
3.
Select 5 to access the System Options.
4.
Select 6 for Daylight Savings.
Automatic Daylight Saving Adjustment
The control panel has an automatic DST (Daylight Saving Time) adjustment feature. If this feature is not enabled (set to No), the Daylight
Saving Time change is not made to the System Clock.
To enable or disable DST adjustment, continue programming:
5.
Select Y (enabled) or N (disabled) by pressing the up or down arrow, then press ENTER.
Daylight Saving Time Start and End
This option allows you to adjust the week and month Daylight Saving Time (DST) for Starts and Ends. For this feature to work, you must
enable (set to Yes) the Automatic Daylight Savings Adjustment option under Daylight Savings Options. The default values for the DST Start
and End are:
DST Start: The second Sunday in March
DST End: The first Sunday in November
To set the start and end for Daylight Saving Time, refer the following steps:
1.
Press the up or down arrow to select the week (1st, 2nd, etc.) Daylight Saving Time starts.
Then, press ENTER to make your selection and move the cursor to the month setting.
2.
Press the up or down arrow to select the month (January – December) Daylight Saving Time starts,.
Then, press ENTER to make your selection and move the cursor to the DST End option.
3.
Press the up or down arrow to select the week (1st, 2nd, etc.) Daylight Saving Time ends.
Then, press ENTER to make your selection and move the cursor to the month setting.
4.
Press the up or down arrow to select the month (January – December) Daylight Saving Time ends.
Then, press ENTER two times to make your selection and exit.
9.6.7 Edit Banner
The Banner is the message that displays on the panel LCD when the System is normal. For example, a System is normal when no alarms or
troubles exist and no one is currently using the System Menus. You can create a custom message, which can be up to 40 characters, two lines
of 20 characters each. If you do not create a custom message, the System will use the Internal Banner. You cannot change the Internal Ban-
ner. To customize the banner display message, do the following.
1.
Enter the Installer Code.
2.
Select 7 to access the Program Menu.
3.
Select 5 to access the System Options.
4.
Select 7 for Edit Banner.
NOTE: See Appendix B for instructions on how to edit the banner.
5.
To select each character of a word, press the up or down arrow. Then, press the right arrow key to move to the next character.
6.
After you enter the word or the sentence, press ENTER to move the cursor to line two of the custom banner.
IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021
Programming
103

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Farenhyt seriesIfp-75hv

Table of Contents