Installing the UPS System
In the following step, DO NOT move the sensing and EMI wires from the rectifier contactor K1
input terminals. These wires must remain connected to the K1 terminals for proper UPS
operation.
11. Disconnect the phase A, B, and C bypass contactor K5 power input leads only (two
12. Connect phase A, B, and C rectifier input power wiring from the utility source to
13. Connect phase A, B, and C, and Neutral (if required) bypass input power wiring
14. If wiring an IDC or IAC, proceed to Step 15; otherwise, proceed to Step 18.
15. Route and connect the output cable between the UPS cabinet and the IDC or IAC.
16. Connect phase A, B, and C, and Neutral (if required) power wiring from the IDC or
17. Proceed to paragraph 3.2.6.3.
18. If wiring a parallel system, proceed to Step 19; otherwise, proceed to Step 21.
Parallel system wiring length should be in accordance with Drawing 164201554-5, sheet
15 of 15, to ensure approximately equal current sharing when in Static Bypass mode.
19. Connect phase A, B, and C, and Neutral (if required) power wiring from the output
20. Proceed to paragraph 3.2.6.3.
21. Connect phase A, B, and C, and Neutral (if required) power wiring from the output
22. Proceed to paragraph 3.2.6.3.
3-8
EATON Powerware
1/0 AWG wires per phase) from the rectifier contactor K1 input terminals. Connect
these power leads to the bypass input terminals.
the rectifier input terminals in the UPS cabinet. See Appendix A for wiring and
termination requirements and wiring access information. Note wiring connections
for dual-feed systems.
from the utility source to the bypass input terminals and neutral terminals in the
UPS cabinet. See Appendix A for wiring and termination requirements and wiring
access information. Note wiring connections for dual-feed systems.
Refer to the applicable IDC or IAC installation and operation manual, referenced in
paragraph 1.5 on page 1-6, for wiring instructions. See Appendix A for UPS cabinet
wiring access information.
IAC to the UPS cabinet output and neutral terminals. See Appendix A for wiring
and termination requirements.
and neutral terminals of each uninterruptible power module (UPM) to the module
tie cabinet. See Appendix A for UPM wiring and termination requirements and
wiring access information.
and neutral terminals to the critical load. See Appendix A for wiring and
termination requirements and wiring access information.
9390 UPS (100–160 kVA) Installation and Operation Manual S 164201554 Rev E powerware.com
®