Table G. INPUT/OUTPUT Ratings & External Wiring Requirements for the Powerware
9390---160/160
Basic Unit Rating at 0.9 lagging pF load
Input and Bypass Input
Output
AC Input to UPS Rectifier (0.98 min. pF)
Full Load Current plus Battery Recharge Current
(3) Phases, (1) Ground
Minimum Conductor Size
Number per Phase
AC Input to UPS Bypass
Full Load Current
(3) Phases, (1) Neutral---if required, (1) Ground
Minimum Conductor Size
Number per Phase
DC Input from Battery to UPS
(1) Positive, (1) Negative
Minimum Conductor Size
Number per Pole
AC Output to Critical Load
Full Load Current
(3) Phases, (1) Neutral---if required, (1) Ground
Minimum Conductor Size
Number per Phase
Neutral Bonding Jumper
Minimum Conductor Size
Number (See Note 7)
NOTE: Callout letters
2 of 6, 4 of 6, 5 of 6, and 6 of 6.
DELTA SOURCES (TN-S) The Powerware 9390 UPS system can be operated only from a delta
supply source that is fully floating and if the neutral-forming transformer kit (PN 103005400) is
installed in the UPS. The UPS cannot be operated from a mid-point or end-point grounded
delta supply source. With this type of supply source, there is no capability to provide an output
neutral. In no circumstances shall a neutral to ground bonding jumper be installed in the UPS.
8.
The UPS cabinet is shipped with a debris shield covering the ventilation grill on top of the
unit. Do not remove the debris shield until installation is complete. However, remove the
shield before operating the UPS. Once the debris shield is removed, do not place objects
on the ventilation grill.
9.
Refer to Section I of this manual for installation instructions.
A-14
EATON Powerware
A
B
C
D
---
A
B
C
,
,
, and
9390 UPS (100–160 kVA) Installation and Operation Manual S 164201554 Rev E powerware.com
®
Units
kVA
kW
VOLTS
VOLTS
Amps
AWG or kcmil
(each)
Amps
AWG or kcmil
(each)
Vdc
Amps@ (2.0V/cell)
AWG or kcmil
(each)
Amps
AWG or kcmil
(each)
AWG or kcmil
(each)
D
map to Drawing 164201554 ---4, sheets 1 of 6,
C A U T I O N
DESCRIPTION:
POWER WIRING INSTALLATION NOTES
DRAWING NO:
164201554---5
REVISION:
D
Rating 50/60 Hz
160
160
144
144
208/220
480
208/220
480
480
210
400
1/0
(2)
(2)
444/420
192
400
1/0
(2)
(2)
384---480
432---480
403
403
250
250
(2)
(2)
444/420
192
400
1/0
(2)
(2)
1/0
2
(2)
(2)
SHEET:
DATE:
032406
3 of 15