Installation Information
7.
The basic environmental requirements for operation of the UPS system are:
Ambient Temperature Range:
Recommended Operating Range: 20 ---25˚C (68 ---77˚F)
Maximum Relative Humidity:
The UPS ventilation requirements are shown in Table C.
Table C. Air Conditioning or Ventilation Requirements During Full Load Operation
Ratings
100 kVA
100 kVA
120 kVA
120 kVA
160 kVA
160 kVA
Ventilation required for cooling air exhaust: approximately 944 liter/sec (2000 cfm).
A-4
EATON Powerware
Voltage
Input
208/220
208/220
480
208/220
208/220
480
208/220
208/220
480
9390 UPS (100–160 kVA) Installation and Operation Manual S 164201554 Rev E powerware.com
®
0 ---40˚C (32 ---104˚F)
95%, noncondensing
BTU/hr
Output
480
480
480
DESCRIPTION:
PHYSICAL FEATURES AND REQUIREMENTS
DRAWING NO:
164201554---2
REVISION:
C
Heat Rejection
1000/hr (kg-cal/hr)
¢
29.6 (7.45)
27.4 (6.90)
35.5 (8.94)
32.8 (8.28)
47.3 (11.9)
43.8 (11.0)
SHEET:
2 of 2
DATE:
081505