10.
Terminals are UL and CSA rated at 90˚C. Refer to Table H and Table I for power cable
terminations, and Table J for conduit requirements. Drawing 164201554 ---7 shows the
location of the power cable terminals inside the UPS cabinet.
Table H. UPS Cabinet Power Cable Terminations for the Powerware 9390---120/100,
9390---120/120, 9390---160/100, 9390---160/120 and 9390---160/160
Terminal Function
AC Input to UPS Rectifier
and Bypass
(Single Input)
AC Input to UPS Rectifier
(Dual Input)
AC Input To Bypass
(Dual Input)
Single-Feed to Dual-Feed
Wire Transfer from
Rectifier Input Terminals
to Bypass Input Terminals
AC Output to
Critical Load
DC Input from
Battery to UPS
Input and Output Neutral
Customer Ground
NOTE: Customer ground can be run in any conduit listed in Table J.
EATON Powerware
9390 UPS (100–160 kVA) Installation and Operation Manual S 164201554 Rev E powerware.com
®
(208V/220V Input and 208V/220V Output)
Size of Pressure
Terminal Function
Termination
E1
Phase A
2 --- 2/0---500 kcmil
E2
Phase B
2 --- 2/0---500 kcmil
E3
Phase C
2 --- 2/0---500 kcmil
E1
Phase A
2 --- 2/0---500 kcmil
E2
Phase B
2 --- 2/0---500 kcmil
E3
Phase C
2 --- 2/0---500 kcmil
E6
Phase A
2 --- #2---600 kcmil
E7
Phase B
2 --- #2---600 kcmil
E8
Phase C
2 --- #2---600 kcmil
Rectifier
Phase A
Bypass
Phase A
Rectifier
Phase B
Bypass
Phase B
Rectifier
Phase C
Bypass
Phase C
E9
Phase A
2 --- 2/0---500 kcmil
E10
Phase B
2 --- 2/0---500 kcmil
E11
Phase C
2 --- 2/0---500 kcmil
E4
Positive
2 --- #2---600 kcmil
E5
Negative
2 --- #2---600 kcmil
E12
Neutral
8 --- #2---600 kcmil
Ground
Ground
8 --- #14---1/0
DESCRIPTION:
DRAWING NO:
REVISION:
Installation Information
Tightening
Torque
Nm (lb in)
31.1 (275)
31.1 (275)
31.1 (275)
31.1 (275)
31.1 (275)
31.1 (275)
56.5 (500)
56.5 (500)
56.5 (500)
N/A
12.5 (110)
N/A
12.5 (110)
N/A
12.5 (110)
N/A
12.5 (110)
N/A
12.5 (110)
N/A
12.5 (110)
31.1 (275)
31.1 (275)
31.1 (275)
56.5 (500)
56.5 (500)
56.5 (500)
5.6 (50)
POWER WIRING INSTALLATION NOTES
164201554---5
DATE:
C
Type
Screw
4 mm Hex
4 mm Hex
4 mm Hex
4 mm Hex
4 mm Hex
4 mm Hex
1/2 in. Hex
1/2 in. Hex
1/2 in. Hex
M8 Hex Bolt
M8 Hex Bolt
M8 Hex Bolt
M8 Hex Bolt
M8 Hex Bolt
M8 Hex Bolt
4 mm Hex
4 mm Hex
4 mm Hex
1/2 in. Hex
1/2 in. Hex
1/2 in. Hex
Slotted
SHEET:
4 of 15
081505