Installation Information
Table J. Power Cable Conduit Requirements (Cont'd)
UPS Model
Voltage
208/220
Powerware
9390---160/160
Powerware
9390---160/160
A-18
EATON Powerware
Terminal
AC Input to UPS
(A, B, C, Gnd)
AC Input to Bypass
AC
(A, B, C, Neut, Gnd)
Output
(A, B, C, Neut, Gnd)
Battery
(Positive), (Negative), Gnd
DC
AC Input to UPS
(A, B, C, Gnd)
AC Input to Bypass
480
(A, B, C, Neut, Gnd)
AC
Output
(A, B, C, Neut, Gnd)
Battery
DC
(Positive), (Negative), Gnd
9390 UPS (100–160 kVA) Installation and Operation Manual S 164201554 Rev E powerware.com
®
Number of
Wires in
Conduit
4
5
5
5
4
5
5
5
DESCRIPTION:
POWER WIRING INSTALLATION NOTES
DRAWING NO:
164201554---5
REVISION:
C
Minimum Conduit
Number of
Trade Size (inches)
Conduits
3-1/2
3-1/2
3-1/2
2-1/2
2
2
2
2-1/2
SHEET:
DATE:
081505
2
2
2
1
2
2
2
1
7 of 15