UPS Operating Instructions
Do not attempt to restart the system after Load Off until the cause of the shutdown has been
identified and cleared.
3. To restart the UPS after pressing the LOAD OFF pushbutton, follow the procedure
10.2.9 Using the Parallel System Remote Emergency Power-off Switch
A parallel system emergency power-off is initiated by the REPO pushbutton switch. In an
emergency, you can use this switch to control the UPM outputs. The REPO switch
de-energizes the critical load and powers down the UPMs immediately, without asking for
verification.
The UPMs, including Bypass, remain off until restarted.
All power to the critical load is lost when the
You should use this feature only when you want to de-energize the critical load.
NOTE
customer-supplied REPO switch is used, it may not activate in the same manner; refer
to the operating instructions provided with the switch.
To use the REPO switch:
1. Press the REPO pushbutton switch.
Do not attempt to restart the system after Load Off until the cause of the shutdown has been
identified and cleared.
2. To restart the UPMs after using the REPO pushbutton, reset the REPO switch and
10-14
EATON Powerware
in paragraph 10.2.1 or 10.2.2.
The following instructions are for the Powerware-supplied REPO switch. If a
The input, output, and bypass backfeed contactors open, the battery breaker or
disconnect is tripped, and the power module is turned off immediately, without
asking for verification.
then follow the procedure in paragraph 10.2.1 or 10.2.2.
9390 UPS (100–160 kVA) Installation and Operation Manual S 164201554 Rev E powerware.com
®