Chapter 10
The following procedures provide instructions for operating the UPS or parallel system. For
a description of the UPS control panel functions, see Chapter 9, "Using the Control Panel."
10.1 Single Module Operation
10.1.1 Starting the UPS in Normal Mode
To start the UPS system, perform the following procedure:
EATON Powerware
9390 UPS (100–160 kVA) Installation and Operation Manual S 164201554 Rev E powerware.com
®
UPS Operating Instructions
Before starting the UPS or parallel system, ensure all installation tasks are
NOTE
complete and a preliminary startup has been performed by authorized service
personnel. The preliminary startup verifies all electrical interconnections to ensure the
installation was successful and the system operates properly.
Read this section of the manual and have thorough knowledge of parallel and
NOTE
UPS operation before attempting to operate any of the controls.
The UPS displays two minutes of battery runtime at the initial startup. After a
NOTE
24-hour charging period, the UPS automatically runs a battery test and the correct
battery runtime displays.
1. Close the UPS input feeder circuit breaker.
2. If the UPS is dual feed, close the UPS Bypass input feeder circuit breaker.
3. Observe the UPS control panel display becoming active, indicating logic power.
4. Press the CONTROLS pushbutton on the main menu bar. The System Controls
screen appears.
5. On the System Controls screen, the power module (PM) status should indicate
SHUTDOWN.
6. Press the NORMAL pushbutton on the System Controls menu bar.
If Auto Bypass is enabled, the critical load is immediately supplied by the bypass
source, in Bypass mode, until the inverter turns on and the UPS transfers to
Normal mode. The status indicator on the UPS control panel indicates the UPS is
in Bypass mode. If Auto Bypass is not enabled, the UPS output remains off until
the UPS transfers to Normal mode.