Eaton Powerware 9390-160/100 Installation And Operation Manual page 201

Table of Contents

Advertisement

1.
Use Class 1 wiring methods (as defined by the NEC) for interface wiring.
2.
Use Class 2 wiring methods (as defined by the NEC) for interface wiring from 30 to 600V.
3.
When installing external interface wiring (for example, building alarm, relay output, battery
breaker trip, and X-Slot) to the UPS interface terminals, conduit must be installed between
each device and the UPS cabinet. Install the interface wiring in separate conduit from the
power wiring.
4.
When installing internal interface wiring to X-Slot terminals, route the wiring through the
internal opening in the X-Slot communication bay.
5.
All building alarm inputs or remote features require an isolated normally-open contact or
switch (rated at 24 Vdc, 20 mA minimum) connected between the alarm input and
common terminal as shown. All control wiring and relay and switch contacts are
customer-supplied. Use twisted-pair wires for each alarm input and common.
6.
The building alarms can be programmed to display the alarm functional name.
7.
See Table R through Table X and Chapters 3, 5, and 6 for customer interface wiring.
8.
LAN and telephone drops for use with X-Slot connectivity cards must be provided by
facility planners or the customer.
Table R. TB1 and TB2 Interface Connections
Terminal TB1
1
2
3
4
5
6
7
8
9
10
Terminal TB2
1
2
3
4
5
6
7
8
9
10
NOTE: "RETURN" INDICATES CONNECTION TO ELECTRONICS CIRCUIT GROUND: "COMMON" INDICATES
CONNECTION TO COMMON SIDE OF ISOLATED RELAY CONTACT.
EATON Powerware
9390 UPS (100–160 kVA) Installation and Operation Manual S 164201554 Rev E powerware.com
®
Name
Remote EPO NC
Remote EPO Return
Remote EPO NO
Remote EPO Return
Batt Breaker Aux
Batt Breaker Aux Return
Battery UVR (+)
Battery UVR (---)
Building Alarm 1
Building Alarm 1 Return
Name
Building Alarm 2
Building Alarm 2 Return
On Bypass NO
On Bypass Common
Alarm Relay NC
Alarm Relay Common
Alarm Relay NO
Alarm Relay Common
On Inverter NC
On Inverter Common
DESCRIPTION:
DRAWING NO:
REVISION:
Description
Input: Normally-closed dry contact to activate EPO
of UPS from a remote switch
Input: Normally-open dry contact to activate EPO of
UPS from a remote switch
Input: Normally-open contact to indicate when UPS
UVR battery breaker is open.
Output: Fused 48 Vdc source to control operation
of Battery Breaker UVR function. Must be replaced
with same type and rating fuse.
Input: Programmable UPS alarm, activated by a
remote dry contact closure.
Description
Input: Programmable UPS alarm, activated by a
remote dry contact closure. Dedicated for Pull
Chain function when part of Parallel System.
Output: Normally-open contact closes when UPS is
on bypass. Dedicated for Pull Chain function when
part of Parallel System.
Output: General purpose normally-closed relay
contact.
Output: General purpose normally-open relay
contact.
Output: Normally-closed contact opens when
output contactor closes.
INTERFACE WIRING INSTALLATION
NOTES AND TERMINAL LOCATIONS
164201554---8
E
Installation Information
SHEET:
1 of 13
DATE:
032406
A-33