Eaton Powerware 9390-160/100 Installation And Operation Manual page 192

Table of Contents

Advertisement

Installation Information
Table P. INPUT/OUTPUT Ratings for Powerware 9390---120/120 and 9390---160/120 Parallel Systems
Configuration
Basic Unit Rating at 0.9 lagging pF load
Input and Bypass Input
Output
AC Input from UPM
Full Load Current for each Module
(3) Phases, (1) Neutral---if required, (1) Ground
All
Minimum Conductor Size for each Module
Number per Phase for each Module
AC Input to Tie Cabinet Bypass (optional)
Full Load Current
(3) Phases, (1) Neutral---if required, (1) Ground
AC Output to Critical Load
1+1
Full Load Current
(3) Phases, (1) Neutral---if required, (1) Ground
System Neutral Bonding Jumper
Minimum Conductor Size
Number (See Note 27)
AC Input to Tie Cabinet Bypass (optional)
Full Load Current
(3) Phases, (1) Neutral---if required, (1) Ground
2+0
AC Output to Critical Load
and
Full Load Current
2+1
(3) Phases, (1) Neutral---if required, (1) Ground
System Neutral Bonding Jumper
Minimum Conductor Size
Number (See Note 27)
AC Input to Tie Cabinet Bypass (optional)
Full Load Current
(3) Phases, (1) Neutral---if required, (1) Ground
3+0
AC Output to Critical Load
and
Full Load Current
3+1
(3) Phases, (1) Neutral---if required, (1) Ground
System Neutral Bonding Jumper
Minimum Conductor Size
Number (See Note 27)
AC Input to Tie Cabinet Bypass (optional)
Full Load Current
(3) Phases, (1) Neutral---if required, (1) Ground
AC Output to Critical Load
4+0
Full Load Current
(3) Phases, (1) Neutral---if required, (1) Ground
System Neutral Bonding Jumper
Minimum Conductor Size
Number (See Note 27)
NOTE: Callout letters
and 6 of 6.
A-24
EATON Powerware
D
F
G
,
, and
map to drawing 164201554 ---4, sheets 4 of 6, 5 of 6,
9390 UPS (100–160 kVA) Installation and Operation Manual S 164201554 Rev E powerware.com
®
Units
kVA
kW
VOLTS
VOLTS
Amps
D
AWG or kcmil
(each)
F
Amps
G
Amps
---
AWG or kcmil
(each)
F
Amps
G
Amps
---
AWG or kcmil
(each)
F
Amps
G
Amps
---
AWG or kcmil
(each)
F
Amps
G
Amps
---
AWG or kcmil
(each)
DESCRIPTION:
POWER WIRING INSTALLATION NOTES
DRAWING NO:
164201554---5
REVISION:
E
Rating 50/60 Hz
120
120
108
108
208/220
480
208/220
480
333/315
144
See Table E through
Table G for wire size.
333/315
144
333/315
144
1/0
4
(1)
(1)
666/630
288
666/630
288
3/0
1/0
(1)
(1)
999/945
432
999/945
432
1/0
2/0
(2)
(1)
1332/1260
576
1332/1260
576
2/0
2/0
(2)
(1)
SHEET:
13 of 15
DATE:
032406