Conduit must be installed between the UPM cabinets for parallel interface wiring. Install the
interface wiring in separate conduit from the power wiring.
17.
Use Class 1 wiring methods (as defined by the NEC) for parallel interface wiring. The wire
should be shielded twisted pair, rated for 5 amps maximum.
18.
See Table X and Chapter 6 for Powerware Hot Sync CAN Bridge Card interface wiring.
Table X. Powerware Hot Sync CAN Bridge Card Interface Connections
Terminal J3
1
2
3
4
5
6
7
8
9
10
NOTE: All interface wiring is to be provided
by the customer.
EATON Powerware
9390 UPS (100–160 kVA) Installation and Operation Manual S 164201554 Rev E powerware.com
®
Name
Alarm
Alarm Rtn
Not Used
Not Used
Not Used
TX
TX
CAN L
CAN H
Shield
J3
CONNECTIONS FOR PARALLEL SYSTEM CONTROL
CONNECTIONS FOR RMP II, RIM II, OR SCM II
BUILDING ALARM 2 REPLACEMENT
POWERWARE HOT SYNC CAN BRIDGE CARD
DESCRIPTION:
DRAWING NO:
REVISION:
Description
Programmable UPS alarm. Activated by a remote
dry contact closure.
Not Used
Not Used
Not Used
Remote Monitor Panel II (RMP II), Relay Interface
Module II (RIM II), or Supervisory Contact
Module II (SCM II) connections.
Computer Area Network (CAN) Input for parallel
operation.
INTERFACE WIRING INSTALLATION
NOTES AND TERMINAL LOCATIONS
164201554---8
D
Installation Information
SHEET:
9 of 13
DATE:
081505