Eaton Powerware 9390-160/100 Installation And Operation Manual page 190

Table of Contents

Advertisement

Installation Information
28.
See Drawing 164201554 ---7 for UPM terminal locations and Table H or Table I for
termination requirements.
29.
Setup of the CAN Bridge card for parallel operation must be performed by an authorized
Eaton Customer Service Engineer . Contact service to schedule a date.
30.
For parallel system circuit breaker ratings, see appropriate information in Table N.
31.
For parallel system ratings, see the appropriate information in Table O through Table Q.
Table N. Recommended UPM Output (MOB), Main Output (MIS), and Bypass (MBP)
UPM Model
9390---120/100
9390---160/100
9390---120/120
9390---160/120
9390---160/160
A-22
EATON Powerware
Circuit Breaker Ratings
Configuration
MOB
1+1
500
2+0 and 2+1
500
3+0 and 3+1
500
4+0
500
1+1
500
2+0 and 2+1
500
3+0 and 3+1
500
4+0
500
1+1
600
2+0 and 2+1
600
3+0 and 3+1
600
4+0
600
9390 UPS (100–160 kVA) Installation and Operation Manual S 164201554 Rev E powerware.com
®
Output Voltage
208V/220V
MIS
MBP
500
500
1000
1000
1600
1600
2000
2000
500
500
1000
1000
1600
1600
2000
2000
600
600
1200
1200
2000
2000
2400
2400
DESCRIPTION:
POWER WIRING INSTALLATION NOTES
DRAWING NO:
164201554---5
REVISION:
D
480V
MOB
MIS
MBP
200
200
200
200
400
400
200
600
600
200
800
800
200
200
200
200
400
400
200
600
600
200
800
800
250
250
250
250
500
500
250
800
800
250
1000
1000
SHEET:
DATE:
081505
11 of 15

Advertisement

Table of Contents
loading