Table Q. INPUT/OUTPUT Ratings for Powerware 9390---160/160 Parallel System
Configuration
Basic Unit Rating at 0.9 lagging pF load
Input and Bypass Input
Output
AC Input from UPM
Full Load Current for each Module
(3) Phases, (1) Neutral---if required, (1) Ground
All
Minimum Conductor Size for each Module
Number per Phase for each Module
AC Input to Tie Cabinet Bypass (optional)
Full Load Current
(3) Phases, (1) Neutral---if required, (1) Ground
AC Output to Critical Load
1+1
Full Load Current
(3) Phases, (1) Neutral---if required, (1) Ground
System Neutral Bonding Jumper
Number
AC Input to Tie Cabinet Bypass (optional)
Full Load Current
(3) Phases, (1) Neutral---if required, (1) Ground
2+0
AC Output to Critical Load
and
Full Load Current
2+1
(3) Phases, (1) Neutral---if required, (1) Ground
System Neutral Bonding Jumper
Minimum Conductor Size
Number (See Note 27)
AC Input to Tie Cabinet Bypass (optional)
Full Load Current
(3) Phases, (1) Neutral---if required, (1) Ground
3+0
AC Output to Critical Load
and
Full Load Current
3+1
(3) Phases, (1) Neutral---if required, (1) Ground
System Neutral Bonding Jumper
Minimum Conductor Size
Number (See Note 27)
AC Input to Tie Cabinet Bypass (optional)
Full Load Current
(3) Phases, (1) Neutral---if required, (1) Ground
AC Output to Critical Load
4+0
Full Load Current
(3) Phases, (1) Neutral---if required, (1) Ground
System Neutral Bonding Jumper
Minimum Conductor Size
Number (See Note 27)
NOTE: Callout letters
and 6 of 6.
EATON Powerware
9390 UPS (100–160 kVA) Installation and Operation Manual S 164201554 Rev E powerware.com
®
(See Note 27)
D
F
G
,
, and
map to drawing 164201554 ---4, sheets 4 of 6, 5 of 6,
DESCRIPTION:
DRAWING NO:
REVISION:
Installation Information
Units
kVA
kW
VOLTS
VOLTS
Amps
D
AWG or kcmil
(each)
F
Amps
G
Amps
AWG or kcmil
---
(each)
F
Amps
G
Amps
---
AWG or kcmil
(each)
F
Amps
1332/1260
G
Amps
1332/1260
---
AWG or kcmil
(each)
F
Amps
1776/1680
G
Amps
1776/1680
---
AWG or kcmil
(each)
POWER WIRING INSTALLATION NOTES
164201554---5
DATE:
E
Rating 50/60 Hz
160
160
144
144
208/220
480
208/220
480
444/420
192
See Table E through
Table G for wire size.
444/420
192
444/420
192
2/0
2
(1)
(1)
888/840
384
888/840
384
1/0
1/0
(2)
(1)
576
576
2/0
2/0
(2)
(1)
768
768
3/0
3/0
(2)
(1)
SHEET:
14 of 15
032406
A-25