Confirming Error Messages - Samson 3730 Series Mounting And Operating Instructions

Electropneumatic positioner
Table of Contents

Advertisement

4
Out of specification
The positioner is operated outside speci-
fied operating conditions.
Note: If an event is assigned to the "No
message" status, this event does not have
any effect on the condensed state.
The condensed state appears on the display
with the following icons:
Condensed state
Maintenance alarm
Function check
Maintenance required/
Maintenance demanded
Out of specification
If the positioner has not been initialized, the
maintenance alarm icon (
the display as the positioner cannot follow
its reference variable.
If fault alarms exist, the possible source of
error is displayed in Code 49 onwards. In
this case, Err appears on the display.
The cause and recommended action are
listed in the code list (section 12).
S
Positioner
display
Text, e.g. tESting,
TunE or tESt
blinking
) appears on
Example
Error caused by pin
position
Fault alarm output
The "Maintenance alarm" as the condensed
state causes the optional fault alarm output
to be switched.
4
The "Function check" condensed state
can also switch the fault alarm contact in
Code 32 .
4
The "Maintenance required/demanded"
condensed state can also switch the fault
alarm contact in Code 33 .

8.3.1 Confirming error messages

Enable configuration:
Note: If no settings are entered within
120 seconds, the enabled configuration
function becomes invalid.
→ Code 3
Turn
Press
, Code 3 blinks
→ ON
Turn
Press
, display:
Confirm error messages:
→ Error code which you want to
Turn
confirm.
Press
to confirm the error message.
Operation
69
EB 8384-3 EN

Advertisement

Table of Contents
loading

This manual is also suitable for:

3730-3