Samson 3730 Series Mounting And Operating Instructions page 87

Electropneumatic positioner
Table of Contents

Advertisement

Code
Parameter – Readings,
no.
values [default setting]
Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.
A7 y-monitoring reference
49*
value
A8 Activation delta y-moni-
toring
[No] · YES · ESC
A9 delta y-monitoring value
0 to 100 %, [10 %]
d
Step parameters for the partial stroke test (PST)
d1 – Unassigned
d2 Step start
0.0 to 100.0 %
[95.0 %]
d3 Step end
0.0 to 100.0 %
[90.0 %]
d4 Activation of the ramp
function
[No] · YES
d5 Ramp time (rising)
0 to 9999 s, [15 s]
Display only
The valve moves to the valve position Step start (Code 49 - d2)
and Step end (Code 49 - d3) with certain control pulses. The dif-
ference between these control pulses creates the delta y value
[1/s].
The y-monitoring reference value applies to the adjusted step
values (Code 49 - d2 and Code 49 - d3) and for the selected
ramp times (Code 49 - d5 and Code 49 - d6). The y-monitoring
reference value must be determined again if any of the above
mentioned values change.
Activates/deactivates delta y-monitoring
The percentage [%] of the entire range of the control pulse be-
tween 1 and 10000 1/s (Example: 10 % = 10000 1/s)
The partial stroke test is canceled if the change in control signal
(delta y) varies from the y-monitoring reference value by this
amount.
Start value to perform the step response test
End value to perform the step response test
Activates/deactivates the ramp function.
Ramp time for 0 to 100 % travel (rising) of the ramp function.
Do not enter a ramp time which is lower than the value automati-
cally given during initialization.
Description
Code list
87
EB 8384-3 EN