Samson 3730 Series Mounting And Operating Instructions page 88

Electropneumatic positioner
Table of Contents

Advertisement

Code list
Code
Parameter – Readings,
no.
values [default setting]
Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.
d6 Ramp time (falling)
49*
0 to 9999 s, [15 s]
d7 Settling time before test
start
1.0 to 240.0 s, [10.0 s]
d8 Delay time after step
1.0 to 240.0 s, [2.0 s]
d9 Scan time
0.2 to 250.0 s, [0.2 s]
E
Cancelation conditions of the partial stroke test (PST)
E0 Activation x control
[No] · YES
E1 x control value
–10.0 to 110.0 % of
total trave, [0.0 %]
E2 – Unassigned
E3 – Unassigned
E4 – Unassigned
E5 Activation tolerance
band control
[No] · YES
E6 PST Tolerance band
0.1 to 100.0 %,
[5.0 %]
E7 Max. test duration
30 to 25000 s, [30 s]
F
Partial stroke test (PST) information · Display only
F0 No test available
F1 Test OK
88
EB 8384-3 EN
Ramp time for 0 to 100 % travel (falling) of the ramp function.
Do not enter a ramp time which is lower than the value automati-
cally given during initialization.
Waiting time before the test starts to allow the valve to safely
reach the step start value.
Time after the first step until the second step starts.
Scan time of the step response test
Activates/deactivates x control.
The test is automatically canceled as soon as the valve position
falls below this value.
Activates/deactivate tolerance band control.
The test is automatically canceled as soon as the Step end (Code
49 - d3) exceeds this value.
Maximum time within which a test can be completed before the
test is canceled automatically.
No test exists or the test has been canceled manually.