Advertisement

Code list
Data errors
Error codes – Recommended action Condensed state alarm active, when prompted, Err appears.
Control parameter
68
Status classification [Maintenance required]
Recommended action Confirm error, perform reset and re-initialize the positioner.
69
Poti parameter
Status classification [Maintenance required]
Recommended action Confirm error, perform reset and re-initialize the positioner.
70
Calibration parameter
Status classification [Maintenance required]
Recommended action Return the positioner to SAMSON AG for repair.
71
General parameters
Status classification [Maintenance required]
Recommended action Confirm error.
73
Internal device error 1
Status classification [Maintenance required]
Recommended action Return the positioner to SAMSON AG for repair.
74
HART parameters
Status classification [Maintenance required]
Recommended action Confirm error and perform reset.
75
Info parameters
Status classification [Maintenance required]
Recommended action Return the positioner to SAMSON AG for repair.
96
EB 8384-3 EN
When fault alarms exist, they are displayed here.
Control parameter error
Parameter error of the digital potentiometer.
Error in the production calibration data. Subsequently, the device
runs on default values.
Parameter errors that are not critical for the control.
Check and, if necessary, reset required parameters.
Internal device error
Parameter errors that are not critical for the control.
Error in the info parameters that are not critical for the control.