Samson 3730 Series Mounting And Operating Instructions page 84

Electropneumatic positioner
Table of Contents

Advertisement

Code list
Code
Parameter – Readings,
no.
values [default setting]
Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.
45
Solenoid valve info
YES
HIGH/LOW
No
Bus address
46*
0 to 63 [0]
ESC
Write protection HART
47*
YES, [No], ESC
48*
Diagnostics
Diagnosis parameters d
d0 Temperature
–55 to 125 °C
d1 Minimum temperature
[20 °C]
d2 Maximum temperature
[20 °C]
d3 Number of zero
calibrations
[0]
d4 Number of
initializations
[0]
d5 Zero point limit
0.0 to 100.0 % [5.0 %]
of the nominal range
84
EB 8384-3 EN
Display only,
indicates whether a solenoid valve is installed or not.
If a voltage supply is connected at the terminals of the installed
solenoid valve, YES and HIGH appear on the display in alter-
nating sequence. If a voltage supply is not connected (actuator
vented, fail-safe position indicated on the display by the S icon),
YES and LOW appear on the display in alternating sequence.
Select bus address
When the write protection function is activated, device data can
only be read, but not overwritten over HART
Current operating temperature [°C] inside the positioner
(accuracy ± 3 %)
Display only
The lowest temperature below 20 °C that has ever occurred.
Display only
The highest temperature above 20 °C that has ever occurred.
Display only
The number of zero calibrations since the last initialization.
Display only
The number of initializations that have been performed since the
last reset.
Display only
User-defined zero point monitoring
Used for error monitoring of the zero point shift.
Description
®
communication.