Samson 3730 Series Mounting And Operating Instructions page 89

Electropneumatic positioner
Table of Contents

Advertisement

Code
Parameter – Readings,
no.
values [default setting]
Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.
F2 x cancelation
49*
F3 y cancelation
F4 Tolerance band
exceeded
F5 Max. test time exceeded The test was not completed within the maximum test time and
F6 Test man. canceled
F7 Measured data storage
out of memory
F8 Aborted by int. solenoid
valve
F9 Supply pressure/friction An insufficient supply pressure or excessive friction occurred
h
Application type of valve
h0 Application type
[No] · YES · ESC
h1 Operating point
0.0 to 100.0 % valve
position, [100.0 %]
h2 Limit fail-safe position
0.0 to 20.0 % reference
variable, [12.5 %]
The test was canceled by the x cancelation function.
The test was canceled by the y cancelation function.
The test was canceled. The x-values exceeded the tolerance
band.
was automatically canceled.
The test has been manually canceled by the user.
The maximum capacity of the memory for measured data has
been reached. After 100 measured data per measured variable
have been recorded, the logging stops. However, the test is con-
tinued.
The test was canceled by the activation of the solenoid valve.
during the test.
No
Control valve
YES
Open/close (on/off) valve
Depending on the application type of valve that has been se-
lected, the positioner has different diagnostic functions and be-
haves differently in the automatic mode (AUTO).
The valve moves to this position as soon as the reference variable
exceeds the Limit operating point (Code 49 - h5).
The valves moves to the fail-safe position (SAFE) when the refer-
ence variable falls below this limit.
Description
Code list
89
EB 8384-3 EN