Code list
Code
Parameter – Readings,
no.
values [default setting]
Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.
7*
w/x
[ää] increasing/increasing
äæ increasing/decreasing
ESC
8*
Travel/angle range start
(lower x-range value)
0.0 to 80.0 [0.0] % of the
nominal range
ESC
Note: Specified in mm or
angle ° provided Code 4 is
set
9*
Travel/angle range end
(upper x-range value)
20.0 to 100.0 [100.0] % of
the nominal range
ESC
Note: Specified in mm or
angle ° provided Code 4 is
set
Travel/angle lower limit
10*
(lower x-limit)
0.0 to 49.9 % of the
operating range
[No], ESC
76
EB 8384-3 EN
Direction of action of the reference variable w in relation to the
travel/angle of rotation x
Automatic adaptation:
AIR TO OPEN:
On completing initialization, the direction of action remains in-
creasing/increasing (ää), a globe valve opens as the mA signal
increases.
AIR TO CLOSE:
On completing initialization, the direction of action changes to
increasing/decreasing (äæ), a globe valve closes as the mA
signal increases.
Lower range value for the travel/angle of rotation in the nominal
or operating range.
The operating range is the actual travel/angle of the control
valve and is limited by the lower x-range value (Code 8) and the
upper x-range value (Code 9).
Usually, the operating range and the nominal range are iden-
tical. The nominal range can be limited to the operating range by
the lower and upper x-range values.
Value is displayed or must be entered.
The characteristic is adapted. See also the example in Code 9!
Upper range value for the travel/angle of rotation in the nominal
or operating range.
Value is displayed or must be entered.
The characteristic is adapted.
Example: The operating range is modified, for example, to limit
the range of a control valve which has been sized too large. For
this function, the entire resolution range of the reference variable
is converted to the new limits. 0 % on the display corresponds to
the adjusted lower limit and 100 % to the adjusted upper limit.
Limitation of the travel/angle of rotation downwards to the en-
tered value, the characteristic is not adapted.
The characteristic is not adapted to the reduced range. See also
example in Code 11.