Samson 3730 Series Mounting And Operating Instructions page 71

Electropneumatic positioner
Table of Contents

Advertisement

Software adaptation
Code 38 (inductive alarm is set to YES ).
The inductive limit switch is connected to the
terminals +41/–42.
The device is set up accordingly when deliv-
ered ex works SAMSON.
Setting the switching point:
NOTICE
During adjustment or testing, the switching
point must always be approached from
mid-position (50 %).
To ensure safe switching under any ambient
conditions, the switching point should be
adjusted to a value of approx. 5 % before
the mechanical stop (OPEN – CLOSED).
For CLOSED position:
1. Initialize positioner.
2. Use the MAN function to move the
positioner to 5 % (see LC display).
3. Adjust the tag using the yellow adjust-
ment screw (2) until the tag enters or
leaves the field and the switching ampli-
fier responds. You can measure the
switching voltage as an indicator.
Contact function:
4
Tag leaving the field > contact is made
4
Tag entering the field > contact is
opened.
For OPEN position:
1. Initialize positioner.
2. Use the MAN function to move the
positioner to 95 % (see LC display).
3. Adjust the tag (1) using the yellow ad-
justment screw (2) until the tag enters or
leaves the field of the proximity switch
(3).
You can measure the switching voltage
as an indicator.
Contact function:
4
Tag leaving the field > Contact is made.
4
Tag entering the field > Contact is
opened.
Adjusting the limit switch
EB 8384-3 EN
71

Advertisement

Table of Contents
loading

This manual is also suitable for:

3730-3

Table of Contents