Samson 3730 Series Mounting And Operating Instructions page 75

Electropneumatic positioner
Table of Contents

Advertisement

Code
Parameter – Readings,
no.
values [default setting]
Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.
4*
Pin position
[No]
17, 25, 35, 50, 70, 100,
200 mm
90° with rotary actuators
ESC
Note: If you select a pin
position in Code 4 that is too
small, the positioner switches
to SAFE mode for reasons of
safety
Nominal range
5*
[15.0] mm or angle °
ESC
6*
Init mode
[MAX]
NOM
MAN
SUb
ZP
ESC
The follower pin must be inserted into the correct pin position ac-
cording to the valve travel/angle of rotation.
For initialization using NOM or SUb, this pin position must be
entered.
Pin position
Code 4
17
25
35
50
70
100
200
90°
For initialization using NOM or SUb, the nominal travel/angle of
rotation of the valve must be entered.
The permissible adjustment range depends on the pin position
according to the table for Code 4.
After initialization has been successfully completed, the maximum
nominal travel/angle reached on initialization is displayed.
Select the initialization mode
MAX:
Travel/angle of the closure member from the CLOSED
position to the opposite stop in the actuator.
NOM: Travel/angle of the closure member measured from the
CLOSED position to the indicated OPEN position.
MAN: Manually selected range
SUb:
Substitute calibration (without initialization)
ZP:
Zero calibration
Description
Standard
Adjustment range
Code 5
Code 5
7.5
3.6 to 17.7
7.5
5.0 to 25.0
15.0
7.0 to 35.4
30.0
10.0 to 50.0
40.0
14.0 to 70.7
60.0
20.0 to 100.0
120.0
40.0 to 200.0
90.0
24.0 to 100.0
Code list
75