Code list
Code
Parameter – Readings,
no.
values [default setting]
Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.
h3 Lower limit test start
49*
[25.0 % reference
variable]
h4 Upper limit test start
[50.0 % reference
variable]
h5 Limit operating point
55.0 to 100.0 % refe-
rence variable, [75.0 %]
h6 – Unassigned
h7 Limit value time analysis
0.6 to 30.0 s, [0.6 s]
h8 Limit value travel
analysis
0.1 to 100.0 % valve
position, [0.3 %]
h9 Status classification
Close/open
[C] · OK · CR · b · S
ESC
Note: The error codes listed in following appear in the display corresponding to their status
classification set over the condensed state (Maintenance required/Maintenance demanded:
, Out of specification:
to the error code as the status classification, the error is not included in the condensed state.
A status classification is assigned to every error code in the default setting. The status classifi-
cation of error codes can also be changed as required using an operating software (e.g.
TROVIS-VIEW). Refer to section 13.6.
90
EB 8384-3 EN
Display only
The valve remains in its last valid position when the reference
variable is between the Limit fail-safe position and Lower limit
test .
A partial stroke test is started when the reference variable moves
to the range between Lower limit test and Upper limit test and re-
mains there longer than six seconds.
Display only
The valve remains in its last valid position when the reference
variable is between the Upper limit test and Limit operating point .
The valve moves to the Operating point when the reference vari-
able exceeds the Limit operating point .
Time limit for the difference between the reference value and the
latest recorded value. It determines at which difference value an
alarm is to be generated.
Travel limit for the difference between the reference value and the
latest recorded value. It determines at which difference value an
alarm is to be generated.
C
Maintenance required
OK No message
CR Maintenance demanded
b
Maintenance alarm
S
Out of specification
blinking, Maintenance alarm:
Description
). If "No message" is assigned

Advertisement

Table of Contents
loading