13.6 Status classification

Alarms are classified in the positioner with a status when an error occurs. States include
"Maintenance alarm", "Maintenance required", "Maintenance demanded ", "Out of specifi-
cation" and "No message".
4
Maintenance alarm
The positioner cannot perform its control task due to a functional fault in the device or in
one of its peripherals or an initialization has not yet been successfully completed.
4
Maintenance required
The positioner still performs its control task (with restrictions). A maintenance demand or
above average wear has been determined. The wear tolerance will soon be exhausted or
is reducing at a faster rate than expected. Maintenance is necessary in the medium term.
4
Maintenance demanded
The positioner still performs its control task (with restrictions). A maintenance demand or
above average wear has been determined. The wear tolerance will soon be exhausted or
is reducing at a faster rate than expected. Maintenance is necessary in the short term.
4
Out of specification
The positioner is operated out of specification.
4
No message
When this classification is active, it does not have any affect on the condensed state.
You can change the status classification in the Positioner folder (> Error control > Classifica-
tion report ).
Status classification of a single alarm
Maintenance alarm
Maintenance required/demanded
Out of specification
No message
Settings in TROVIS-VIEW software
TROVIS-VIEW3/DTM
red
blue
yellow
white