Code list

12
Code list
Parameter – Readings,
Code
no.
values [default setting]
Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.
0
Operating mode
[MAN] Manual mode
AUtO
Automatic mode
SAFE
Fail-safe position
ESC
Escape
1
Manual w
0 to 100 [0] %
of the nominal range
Reading direction
2
[Normal] or upside down
ESC
Enable configuration
3
[No] YES ESC
74
EB 8384-3 EN
Switchover from automatic to manual mode is smooth.
In fail-safe mode, S appears on the display.
In MAN and AUtO mode, the system deviation is represented by
the bar graph elements.
When the positioner is initialized, the numerical display indicates
the valve position or the angle of rotation in %, otherwise the po-
sition of the lever in relation to the central axis is displayed in de-
grees °.
Adjust the manual set point with the rotary pushbutton, the
current travel/angle is displayed in % when the positioner is ini-
tialized, otherwise the position of the lever in relation to the cen-
tral axis is indicated in degrees °.
Note: Can only be selected when Code 0 = MAN
The reading direction of the display is turned by 180°.
Enables the option to modify data (automatically deactivated when
the rotary pushbutton has not been operated for 120 s.)
HART blinks on the display when the on-site operation is locked.
Codes marked with an asterisk (*) can only be read and not
overwritten.
Likewise, codes can only read over the SSP interface.