Samson Series 3730 Mounting And Operating Instructions

Samson Series 3730 Mounting And Operating Instructions

Electropneumatic
Table of Contents

Advertisement

Series 3730
Electropneumatic Positioner
Type 3730-2
Fig. 1 · Type 3730-2
Mounting and
Operating Instructions
EB 8384-2 EN (1300-1611)
Firmware version 1.54
Edition February 2012

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Series 3730 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Samson Series 3730

  • Page 1 Series 3730 Electropneumatic Positioner Type 3730-2 Fig. 1 · Type 3730-2 Mounting and Operating Instructions EB 8384-2 EN (1300-1611) Firmware version 1.54 Edition February 2012...
  • Page 2 Definitions of the signal words used in these instructions DANGER! NOTICE indicates a hazardous situation which, if not indicates a property damage message. avoided, will result in death or serious injury. Note: Supplementary explanations, information and tips WARNING! indicates a hazardous situation which, if not avoided, could result in death or serious in- jury.
  • Page 3: Table Of Contents

    Contents Contents Page Important safety instructions ..... . 8 Article code ......9 Design and principle of operation .
  • Page 4 Contents Start-up – Settings......50 Defining the valve closed position ....51 Setting the volume restriction Q .
  • Page 5 Contents 15.4.2 Online operation (direct data transmission) ....105 15.4.3 Setting parameters ......106 15.5 Initializing the positioner .
  • Page 6 Modifications of positioner firmware Modifications of positioner firmware in comparison to previous versions Previous 1.00 1.10 The serial interface and serial interface adapter allow the positioner to be operated and configured using TROVIS-VIEW software The following additional status messages were implemented: Code 76 - No emergency mode Code 77 - Program loading error Displays number of zero calibrations performed since the last initialization.
  • Page 7 Modifications of positioner firmware Modifications of positioner firmware in comparison to previous versions Previous 1.42 1.51 Setting can be performed at the positioner to determine whether the valve is to operate as a control valve or an on/off (open/close) valve (see section 3.1) All EXPERTplus diagnostic functions are available in the positioner without having to activate them first (refer to EB 8389 EN on EXPERTplus valve diagnostics) Optional binary input with following actions (refer to EB 8389 EN on EXPERTplus valve...
  • Page 8: Important Safety Instructions

    Important safety instructions Important safety instructions For your own safety, follow these instructions concerning the mounting, start-up and opera- tion of the positioner: The positioner is to be mounted, started up or operated only by trained and experienced personnel familiar with the product. According to these Mounting and Operating Instructions, trained personnel refers to individuals who are able to judge the work they are assigned to and recognize possible dangers due to their specialized training, their knowledge and experience as...
  • Page 9: Article Code

    Article code Article code Article code Type 3730-2 x x x x x 0 x x 0 x 0 0 x 0 x x With LC display, autotune Explosion protection Without ATEX: II 2G Ex ia IIC T6, II 2D Ex tD A21 IP65 T80 °C FM/CSA: Class I, Zone 0 AEx ia IIC;...
  • Page 10: Design And Principle Of Operation

    Design and principle of operation Design principle booster (7) and the electronic unit with a microcontroller (5). operation The standard positioner is fitted with three The electropneumatic positioner is attached binary contacts: A fault alarm output indi- to pneumatic control valves. It is used to as- cates a fault to a control station and two sign the valve stem position (controlled vari- configurable software limit switches are...
  • Page 11: Application Type

    The positioner follows the reference types of attachment using the corresponding variable given over local operation. accessories: Direct attachment to SAMSON The application type is set in Code 49 - h Type 3277 Actuator: Section 4.1 (see section 7.8). Attachment to actuators acc. to IEC 60534-6 (NAMUR): Section 4.2...
  • Page 12: Additional Equipment

    Design and principle of operation Additional equipment External position sensor In this version, only the sensor is mounted to Solenoid valve the control valve. The positioner is located separately from the valve. If the operating voltage for the solenoid The connection of x and y signals to the valve (12) fails, the supply pressure for the valve is established by cable and piping for i/p converter is vented to the atmosphere.
  • Page 13: Configuration Using Trovis-View Software

    Design and principle of operation Configuration using No action is started if the positioner is in the fail-safe position (SAFE). TROVIS-VIEW software Start data logger The data logger is started when the bi- Refer to Table 5 on page 42 for order num- nary input is active (refer to EB 8389 EN bers.
  • Page 14: Technical Data

    Design and principle of operation Technical data Type 3730-2 Positioner (technical data in test certificates additionally apply for explosion-protected devices) Direct attachment to Type 3277: 3.6 to 30 mm Travel, adjustable Attachment acc. to IEC 60534-6: 3.6 to 200 mm Rotary actuators: 24°...
  • Page 15 Type 3730-21xxxx0xx0x00x012: Ex ia IIC T4/T5/T6; IP 54 and IP 65 T80°C GOST Type 3730-21xxxx0xx0x00x014: 0Ex ia IIC T6 X Communication (local) SAMSON SSP interface and serial interface adapter Software requirements TROVIS-VIEW with database module 3730-2 Binary contacts 2 software limit switches, reverse polarity protection, floating, configurable switching characteristics,...
  • Page 16 Design and principle of operation Options for Type 3730-2 Positioner Solenoid valve · Approval acc. to IEC 61508/SIL 24 V DC reverse polarity protection, static destruction limit 40 V; Input 5.7 V Current consumption I = (corresponding to 4.8 mA at 24 V/114 mW) 3840 Signal "0"...
  • Page 17 Design and principle of operation Binary input · Galvanically isolated · Switching behavior configured over software (e.g. TROVIS-VIEW, DTM) Active switching behavior (default setting) Connection For external switch (floating contact) or relay contacts Electrical data Open-circuit voltage when contact is open: max. 10 V, pulsed DC current, peak value 100 mA and RMS value of 0.01 mA when contact is closed Contact...
  • Page 18: Attachment To The Control Valve - Mounting Parts And Accessories

    The positioner is standard equipped with the lever M (pin position 35). The positioner is suitable for the following types of attachment: Direct attachment to SAMSON Type 3277 Actuator Attachment to actuators according to IEC 60534-6 (NAMUR) Attachment to Type 3510 Micro-flow...
  • Page 19 [cm²] [mm] Min. Travel Max. 25.0 120/240/350 35.0 355/700 10.0 50.0 Attachment according to IEC 60534-6 (NAMUR) SAMSON valves/Type 3271 Actuator Other valves/actuators Required Assigned Actuator size Rated travel lever pin position [cm²] [mm] min. Travel max. 60 and 120 with 18.0...
  • Page 20: Direct Attachment

    Attachment to the control valve – Mounting parts and accessories Direct attachment tion. Make sure that the bonded gasket (14) points towards the actuator yoke. 4.1.1 Type 3277-5 Actuator 5. 15 mm travel: Keep the follower pin (2) at lever M (1) on the back of the Refer to Table 1 on page 40 for the required positioner in the pin position 35 (deliv- mounting parts as well as the accessories.
  • Page 21 Attachment to the control valve – Mounting parts and accessories Lever Symbols Switchover plate (9) 1.1 Nut 1.2 Disk spring Actuator stem Follower pin extends Follower clamp Vent plug Attachment left Attachment right Stopper Connecting plate Actuator stem 6.1 Seal rings retracts Pressure gauge bracket Press.
  • Page 22: Type 3277 Actuator

    Attachment to the control valve – Mounting parts and accessories 4.1.2 Type 3277 Actuator and open the positioner cover to hold the positioner shaft in position at the cap Refer to Table 2 on page 41 or the required or the switch (Fig. 19). The lever (1) must mounting parts as well as the accessories.
  • Page 23 Attachment to the control valve – Mounting parts and accessories Lever Connection block 12.1 Screw Disk spring 12.2 Stopper or connection for 10 14 external piping Follower pin Switch plate Follower clamp Gasket Cover plate 11 11.1 Formed seal Cover Gasket 11.1 Vent plug Lever M...
  • Page 24: Attachment According To Iec 60534-6 (Namur)

    Attachment to the control valve – Mounting parts and accessories Attachment according to 3. Mount connecting plate (6) or pressure IEC 60534-6 (NAMUR) gauge bracket (7) with pressure gauges (8) on the positioner, making sure both Refer to Table 3 on page 41 for the required seal rings (6.1) are seated properly.
  • Page 25 Attachment to the control valve – Mounting parts and accessories Attachment to rod-type yoke Rod diameter 20 to 35 mm Attachment to NAMUR rib Additional bracket for actuators with 2800 cm and travel ³ 60 mm Lever Lever L or XL 14.1 Disk spring Follower pin...
  • Page 26: Attachment To Type 3510 Micro-Flow Valve

    Attachment to the control valve – Mounting parts and accessories Attachment to Type 3510 Micro-flow Valve Refer to Table 3 on page 41 for the required mounting parts as well as the accessories. Note the travel table on page 19! The positioner is attached to the valve yoke using a bracket.
  • Page 27 Attachment to the control valve – Mounting parts and accessories Lever Disk spring Follower pin Clamp Connecting clamp Seal rings Pressure gauge bracket Pressure gauge mounting kit Bracket Screw Note: Always use the connecting plate (6) included in the accessories to connect supply and output.
  • Page 28: Attachment To Rotary Actuators

    90°. Prior to attaching the positioner to the 7. Place positioner on the top pair of SAMSON Type 3278 Rotary Actuator, brackets (10) and screw tight. Con- mount the associated adapter (5) to the free end of the rotary actuator shaft.
  • Page 29 Attachment to the control valve – Mounting parts and accessories (7, 8) 10.1 80 mm Note: Always use the connecting plate (6) included in the accessories to connect 130 mm supply and output. Never screw threaded parts directly into the Slot housing.
  • Page 30: Heavy-Duty Version

    (11) underneath, if der no.1400-6964) into the signal pres- necessary. sure output of the positioner (or the out- 2. For SAMSON Type 3278 and VETEC put of the pressure gauge bracket or S160 Rotary Actuator, screw the adapter connecting plate).
  • Page 31 Actuator shaft or adapter 5.1 Adapter 10.1 10.1 SAMSON Type 3278 Attachment acc. to VDE/VDI 3845 VETEC S160, VETEC R (Sept .2010), level 1, size AA1 to AA4, refer to section 16.1 Fig. 11 · Attachment to rotary actuators (heavy-duty version)
  • Page 32: Reversing Amplifier For Double-Acting Actuators

    5. Use a screwdriver (8 mm wide) to screw positioner must be fitted with a reversing the enclosed filters (1.6) into the con- amplifier, e.g. the SAMSON Type 3710 Re- necting boreholes A and Z. versing Amplifier (see Mounting and Oper- ating Instructions EB 8392 EN).
  • Page 33 Attachment to the control valve – Mounting parts and accessories From the positioner Output 38 Supply 9 Control signals to the actuator Reversing amplifier Connecting plate 1.1 Special screws 6.1 O-rings 6.2 Screws 1.2 Gasket 1.3 Special nuts 1.4 Rubber seal 1.5 Sealing plug 1.6 Filter Fig.
  • Page 34: Attaching An External Position Sensor

    Attachment to the control valve – Mounting parts and accessories Attaching an external Operation and settings are described in sections 7 and 8. position sensor – Since 2009, the back of the position sen- sor (20) is fitted with two pins acting as Refer to Table 6 on p.
  • Page 35 Attachment to the control valve – Mounting parts and accessories version "Actuator stem extends". pin (2) from the travel table on page 19. For the fail-safe position "Actuator stem re- The positioner is delivered with lever M tracts" the connection on the top diaphragm in pin position 35 on the sensor.
  • Page 36: Mounting The Position Sensor With Attachment According To Iec 60534-6

    Attachment to the control valve – Mounting parts and accessories of the follower clamp (3). It must rest on Unthread the nut (1.1) and remove the it with spring force. lever together with the disk spring (1.2) Screw tight the mounting plate (21) onto from the sensor shaft.
  • Page 37: Mounting The Position Sensor To Type 3510 Micro-Flow Valve

    Attachment to the control valve – Mounting parts and accessories the follower plate (3) and fix with the 2. Screw the position sensor (20) onto the screws (14.1). bracket (21). 3. Select the lever S (1) from the accesso- 5. Place the bracket with the sensor at the NAMUR rib in such a manner that the ries and screw the follower pin (2) into follower pin (2) rests in the slot of the fol-...
  • Page 38: Mounting The Position Sensor To Rotary Actuators

    Attachment to the control valve – Mounting parts and accessories 4.6.4 Mounting the position 4. Place the lever (1) and disk spring (1.2) sensor to rotary actuators on the sensor shaft. Place the lever (1) in mid-position and For the required mounting parts and the ac- hold it in place.
  • Page 39: Attaching Positioners With Stainless Steel Housings

    Attachment to the control valve – Mounting parts and accessories Attaching positioners with Air purging function for stainless steel housings single-acting actuators Positioners with stainless steel housings re- The exhaust air from the positioner is di- quire mounting parts that are completely verted to the actuator spring chamber to made of stainless steel or free of aluminum.
  • Page 40: Mounting Parts And Accessories

    Attachment to the control valve – Mounting parts and accessories over piping. An adapter available as an ac- Should other valve accessories be used cessory is used for this purpose: which vent the actuator (e.g. solenoid valve, volume booster, quick exhaust valve), this exhaust air must also be included in the Threaded bushing G ¼...
  • Page 41 Attachment to the control valve – Mounting parts and accessories Table 2 · Direct attachment to Type 3277 (Fig. 5) Order no. Mounting parts For actuators with 240, 350, 355 and 700 cm² 1400-7453 Steel 1400-6444 240 cm² Stainless steel 1400-6445 Required piping with screw fitting Steel...
  • Page 42 1400-9526 Mounting parts Attachment for SAMSON Type 3278 with 160/320 cm², CrNiMo steel bracket 1400-7614 Attachment for SAMSON Type 3278 with 160 cm² and for VETEC Type S160, 1400-9245 Type R and Type M, heavy-duty version 1400-5891 Attachment for SAMSON Type 3278 with 320 cm² and for VETEC Type S320,...
  • Page 43 Attachment to rotary actuators Bracket surface area corresponds to level 2, heavy-duty version 1400-9974 SAMSON Type 3278 with 160 cm² (also for VETEC Type S160 and Type R), 1400-9385 heavy-duty version 1400-5891 SAMSON Type 3278 with 320 cm² and for VETEC Type S320, heavy-duty...
  • Page 44: Connections

    Connections Connections be observed. Blow through all air pipes and hoses thoroughly prior to connecting them. WARNING! Mount the positioner, keeping the following sequence: If the positioner is attached directly to the 1. Remove the protective film from the Type 3277 Actuator, the connection of the pneumatic connections positioner's output pressure to the actuator is 2.
  • Page 45: Signal Pressure (Output)

    Connections Actuator stem retracts FE (Air to close) Electrical connections Fail-safe position "Valve Open" (for globe and angle valves): DANGER! For tight-closing valves, the maximum signal Risk of electric shock and/or pressure pst is roughly estimated as fol- the formation of an explosive lows: atmosphere! –...
  • Page 46 Connections Cable entries In particular, the radial thickness of the con- ductor insulation for common insulation ma- The cable entry with M20 x 1.5 cable gland, terials, such as polyethylene, must have a 6 to 12 mm clamping range. minimum radial thickness of 0.2 mm. There is a second M20 x 1.5 threaded bore The diameter of an individual wire in a in the housing that can be used for addi-...
  • Page 47: Switching Amplifiers

    Connections 5.2.1 Switching amplifiers NOTICE The minimum permissible reference variable For operation of the limit switches, switching should not fall below 3.8 mA for operating amplifiers must be connected in the output the positioner. circuit. To ensure the operating reliability of the positioner, the amplifiers should comply with the limit values of the output circuits Accessories...
  • Page 48: Operator Controls And Readings

    Operator controls and readings Operator controls Readings on display readings Icons appear on the display that are as- signed to parameters, codes and functions. Rotary pushbutton Operating modes: The rotary pushbutton is located underneath Manual mode (MAN), section 8.2.1 the front protective cover. Automatic mode (AUTO), section 8.2.1 The positioner is operated on site using the S Fail-safe position (SAFE), section 8.2.2...
  • Page 49 Operator controls and readings Displays and their meaning AUtO Automatic mode Not available/ Available/Active Not active Clockwise Zero calibration Nominal travel Counterclockwise OVERLOAD w > 22 mA Error Increasing/increasing ää Reset Escape Increasing/decreasing äæ Start ix ³ 21.6 mA SAFE Fail-safe position ix £...
  • Page 50: Serial Interface

    Start-up – Settings Serial interface Start-up – Settings The positioner must be supplied with at least WARNING! 4 mA. Mount the positioner, keeping the following The positioner can be connected directly to sequence: the PC via the local serial interface and the 1.
  • Page 51: Defining The Valve Closed Position

    The position of volume restriction Q also de- pends on how the signal pressure is routed For checking purposes: at the actuator in SAMSON actuators: After successfully completing initialization, the positioner display should read 0 % when The “SIDE“ position applies for actuators...
  • Page 52: Adapting The Display

    Start-up – Settings The “SIDE”restriction position always ap- Turn ® Required direction plies for actuators from other manufac- Press to confirm reading direction. turers. Overview · Position of volume restriction Q* Limiting the signal pressure Transit If the maximum actuator force may cause Signal time <...
  • Page 53: Checking The Operating Range Of The Positioner

    Start-up – Settings Press to confirm the pressure limit set- The angle of rotation on the back of the ting. positioner is indicated. A horizontal lever (mid position) is equal to 0°. Checking the operating To ensure the positioner is working prop- range of the positioner erly, the outer bar elements may not blink while the valve is moving through the oper-...
  • Page 54: Initialization

    Start-up – Settings Initialization NOM nominal range Initialization mode for all globe valves (see section 7.6.2) WARNING! MAN manually selected range During initialization, the control valve moves Initialization mode for globe valves with through its entire travel/rotation range. an unknown nominal range (see section Therefore, do not start the initialization pro- 7.6.3) cedure while a process is running, but only...
  • Page 55: Max - Initialization Based On Maximum Range

    Start-up – Settings The time required for an initialization pro- Valve closed Direction of Valve position action Closed at Open at cess depends on the transit time of the actu- ator and may take several minutes. AIR TO OPEN 100 % ää...
  • Page 56: Nom - Initialization Based On Nominal Range

    Start-up – Settings Enter the pin position: Default No Pin position Default No Turn ® Code 3 , display: No ® Code 3 blinks Press ® Code 4 Turn ® YES Turn , Code 4 blinks Press Press , display Turn ®...
  • Page 57: Man - Initialization Based On A Manually Selected Range

    Start-up – Settings Enable configuration: Turn ® Nominal travel/angle Press Note: If no settings are entered within 120 seconds, the enabled configuration Select the initialization mode: function becomes invalid. Initialization mode Default MAX Default No ® Code 6 Turn Press , Code 6 blinks Turn ®...
  • Page 58 Start-up – Settings (Code 8 ) and travel/angle range end Select the initialization mode: (Code 9 ). Enable configuration: Initialization mode Default MAX Note: If no settings are entered within 120 seconds, the enabled configuration ® Code 6 Turn function becomes invalid. , Code 6 blinks Press ®...
  • Page 59: Sub Substitute Calibration

    Start-up – Settings 7.6.4 SUb substitute calibration A complete initialization procedure takes Default No several minutes and requires the valve to move through its entire travel range several times. This initialization mode, however, is Turn ® Code 3 , display: No an emergency mode, in which the control parameters are estimated and not deter- , Code 3 blinks...
  • Page 60 Start-up – Settings Select the initialization mode: Change pressure limit and control parame- ters: Note: Do not change the pressure limit Initialization mode Default MAX (Code 16). Only change the control param- eters K (Code 17) and T (Code 18) if the settings of the replaced positioner are ®...
  • Page 61 Start-up – Settings Enter closing direction and blocking posi- Start initialization: tion: Press INIT key! The operating mode is changed to MAN . Closing direction Direction of rotation caus- The blocking position is indicated. ing the valve to move to the CLOSED position (view onto positioner display) Note: As initialization has not been carried...
  • Page 62: Zero Calibration

    Start-up – Settings Perform zero calibration: rected. Proceed as follows: to 4 (Code 18). Set T If the positioner still oscillates, the gain K Initialization mode (Code 17) must be decreased until the Default MAX positioner shows a stable behavior. ®...
  • Page 63: Performing Settings For Open/Close Valves

    Start-up – Settings Performing settings for ceeds the Limit operating point , the valve moves to the Operating point ( Code 49 - open/close valves h1). The valve moves back to the fail-safe position if the reference variable then falls If the valve is to be operated using the below the Limit fail-safe position (Code 49 - open/close (on/off) application type, the...
  • Page 64 Start-up – Settings After the test has been canceled, the valve Travel [%] moves back to its last position (fail-safe posi- Code 49 - h1 tion or Operating point ). Code 49 - h5 Performing settings Code 49 - h4 Configuration at the positioner must be en- abled before the application type Code 49 - h3...
  • Page 65: Reset To Default Values

    Start-up – Settings Reset to default values This function resets all parameters to the fac- tory default values (see code list in sec- tion 14). Enable configuration: ® Code 3, display: No Turn Press , Code 3 blinks Turn ® YES Press , display Reset start-up parameters:...
  • Page 66: Operation

    Operation Operation You can now configure codes one after the other: Turn and select the required code. WARNING! The actuator stem moves while the positioner Press to access the selected code. The is being operated. code number starts to blink. Do not touch the actuator stem or obstruct it Turn and select the setting.
  • Page 67: Operating Modes

    Operation Operating modes Adjust the manual reference variable 8.2.1 Automatic and manual modes After initialization has been completed suc- cessfully, the positioner is in automatic ® Code 1 Turn mode. , Code 1 blinks. Press Turn until sufficient pressure has been automatic mode built up in the positioner and the control valve moves to the required position.
  • Page 68: Fail-Safe Position (Safe)

    Operation 8.2.2 Fail-safe position (SAFE) Malfunction/maintenance alarm If you want to move the valve to fail-safe po- sition determined during start-up (see sec- All status and fault alarms are classified tion 7.1), proceed as follows: according to a status in the positioner. The default settings of the status classification are listed in the code list.
  • Page 69: Confirming Error Messages

    Operation Out of specification Fault alarm output The positioner is operated outside speci- The “Maintenance alarm” as the condensed fied operating conditions. state causes the optional fault alarm output to be switched. Note: If an event is assigned to the “No The “Function check”...
  • Page 70: Adjusting The Limit Switch

    Adjusting the limit switch Adjusting the limit switch The desired switching function, i.e. whether the output relay shall be picked up or re- The positioner version with inductive limit leased when the tag has entered the field, switch has one adjustable tag (1) mounted has to be determined, if necessary, at the on the shaft which operates the proximity switching amplifier.
  • Page 71 95 % (see LC display). The device is set up accordingly when deliv- 3. Adjust the tag (1) using the yellow ad- ered ex works SAMSON. justment screw (2) until the tag enters or Setting the switching point: leaves the field of the proximity switch (3).
  • Page 72: Retrofitting An Inductive Limit Switch

    Adjusting the limit switch Retrofitting an inductive limit switch Required retrofit kit: Limit switch Order no. 1400-7460 Note: For explosion-protected devices, the requirements in section 11 need to be kept. 1. Take off the rotary pushbutton (3) and cap (1), unthread the five fixing screws (2) and lift off the plastic cover (9) to- gether with the display, taking care not to damage the ribbon cable (between...
  • Page 73: Maintenance

    Servicing explosion-protected When updates are performed by a service devices employee appointed by SAMSON, the up- date is confirmed on the positioner by the If a part of the device on which the explo- test mark assigned by SAMSON’s Quality sion protection is based needs to be ser- Assurance.
  • Page 74: Maintenance, Calibration And Work On Equipment

    Maintenance, calibration and work on equipment b.) Updates on site: Updates on site are only permitted after the plant operator has presented a sig- ned hot work permit. After updating has been completed, add the current firmware to the nameplate; this can be done using labels.
  • Page 75: Code List

    Code list Code list Parameter – Readings, Code Description values [default setting] Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration. Operating mode Switchover from automatic to manual mode is smooth. In fail-safe mode, S appears on the display. [MAN] Manual mode In MAN and AUtO mode, the system deviation is represented by AUtO...
  • Page 76 Code list Parameter – Readings, Code Description values [default setting] Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration. Pin position The follower pin must be inserted into the correct pin position ac- cording to the valve travel/angle of rotation.
  • Page 77 Code list Parameter – Readings, Code Description values [default setting] Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration. Direction of action of the reference variable w in relation to the travel/angle of rotation x [ää] increasing/increasing äæ...
  • Page 78 Code list Parameter – Readings, Code Description values [default setting] Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration. Travel/angle upper limit Limitation of the travel/angle of rotation upwards to the entered (upper x-limit) value, the characteristic is not adapted.
  • Page 79 Code list Parameter – Readings, Code Description values [default setting] Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration. Reference variable range If w approaches the percentage adjusted at the final value that end (w-end) causes the valve to open, the actuator is immediately completely filled with air (with AIR TO OPEN) or vented (with AIR TO...
  • Page 80 0 to 9 [0] Linear Equal percentage Reverse equal percentage SAMSON butterfly valve linear SAMSON butterfly valve equal percentage VETEC rotary plug valve linear VETEC rotary plug valve equal percentage Segmented ball valve linear Segmented ball valve equal percentage User-defined (defined over operating software) Note: The various characteristics are listed in the Appendix (section 17).
  • Page 81 Code list Parameter – Readings, Code Description values [default setting] Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration. Total valve travel Totaled double valve travel. 0 to 99 · 10 Can be reset to 0 over Code 36 - Std. Exponential reading from 9999 travel Note: The total valve travel is saved in a non-volatile memory cycles onwards...
  • Page 82 Code list Parameter – Readings, Code Description values [default setting] Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration. Limit value A1 Alarm A1 goes into the state of response when the value exceeds the limit.
  • Page 83 Code list Parameter – Readings, Code Description values [default setting] Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration. Fault alarm ix Used to select whether faults causing the fault alarm contact to switch should also be signaled by the position transmitter output [No] and how they should be signaled...
  • Page 84 Code list Parameter – Readings, Code Description values [default setting] Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration. Reset Std: Resets all parameters to default (factory setting) as well as the diagnosis data. After a reset, the positioner must [No] be re-initialized.
  • Page 85 Code list Parameter – Readings, Code Description values [default setting] Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration. Solenoid valve info Display only, indicates whether a solenoid valve is installed or not. If a voltage supply is connected at the terminals of the installed HIGH/LOW solenoid valve, YES and HIGH appear on the display in alter-...
  • Page 86 Code list Parameter – Readings, Code Description values [default setting] Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration. d7 Start reference test Starts reference test for Drive signal y steady-state (d1) and drive signal y hysteresis (d2) (Tests).
  • Page 87 Code list Parameter – Readings, Code Description values [default setting] Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration. Partial stroke test (PST)/Full stroke test (FST) · Application type Partial stroke test (PST) A0 Start Partial Stroke Test Operating mode and PST testing mode must be set to MAN.
  • Page 88 Code list Parameter – Readings, Code Description values [default setting] Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration. A8 Activation delta y-moni- Activates/deactivates delta y-monitoring toring [No] · YES · ESC A9 delta y-monitoring value The percentage [%] of the entire range of the control pulse be- tween 1 and 10000 1/s (Example: 10 % = 10000 1/s)
  • Page 89 Code list Parameter – Readings, Code Description values [default setting] Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration. Cancelation conditions of the partial stroke test (PST) E0 Activation x control Activates/deactivates x control. [No] ·...
  • Page 90 Code list Parameter – Readings, Code Description values [default setting] Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration. F7 Measured data storage The maximum capacity of the memory for measured data has out of memory been reached.
  • Page 91 Code list Parameter – Readings, Code Description values [default setting] Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration. h6 – Unassigned h7 Limit value time analysis Time limit for the difference between the reference value and the latest recorded value.
  • Page 92 Code list Initialization errors Error codes – Recommended action Condensed state alarm active, when prompted, Err appears. When error messages exist, they are displayed here. x > range The value supplied by the measuring signal is either too high or too low, the measuring sensor is close to its mechanical limit.
  • Page 93 Code list Error codes – Recommended action Condensed state alarm active, when prompted, Err appears. When error messages exist, they are displayed here. Initialization time exceeded The initialization routine lasts too long. (Init time >) • No pressure on the supply line or there is a leak. •...
  • Page 94 Code list Operational errors Error codes – Recommended action Condensed state alarm active, when prompted, Err appears. When error messages exist, they are displayed here. Control loop Control loop error, the control valve does not react within the tol- erable times of the controlled variable (tolerance band alarm Code 19).
  • Page 95 Status classification [Maintenance demanded] Recommended action Return the positioner to SAMSON AG for repair. w too small The reference variable is much smaller than 4 mA (0 %); occurs if the power source that drives the positioner does not comply with the standard.
  • Page 96 Valve moves to the fail-safe position. Status classification Maintenance alarm (cannot be classified) Recommended action Return the positioner to SAMSON AG for repair. Test calculation The hardware controller is monitored by means of a test calculation.
  • Page 97 Error in the production calibration data. Subsequently, the device runs on default values. Status classification [Maintenance required] Recommended action Return the positioner to SAMSON AG for repair. General parameters Parameter errors that are not critical for the control. Status classification [Maintenance required] Recommended action Confirm error.
  • Page 98 Status classification Maintenance alarm (cannot be classified) Recommended action Interrupt current and restart positioner. Otherwise, return the positioner to SAMSON AG for repair. Options parameter Errors in options parameters Status classification [Maintenance required] Recommended action Return the positioner to SAMSON AG for repair. EB 8384-2 EN...
  • Page 99 Code list Diagnosis errors Error codes – Recommended action Condensed state alarm active, when prompted, Err appears. When error messages exist, they are displayed here. Extended diagnostics Messages are generated by the extended EXPERTplus diagnostics (refer to EB 8389 EN on EXPERTplus valve diagnostics) Status classification Maintenance required (cannot be classified) Diagnostic parameters Errors that are not critical for control.
  • Page 100: Settings In Trovis-View Software

    Settings in TROVIS-VIEW software 15.1 General The TROVIS-VIEW software allows various smart SAMSON devices to be configured over a common operator interface. It consists of the operator interface, communication server, and the device-specific module. The software has a Windows Explorer ®...
  • Page 101: Installing Trovis-View Software

    Settings in TROVIS-VIEW software 15.2 Installing TROVIS-VIEW software 1. Run setup.exe to install the program. Installing the program from the downloaded ZIP file: Download and unzip the ZIP file on your system before starting the installation. Installing the program from a CD-ROM: Once inserted, the CD-ROM starts the installation program automatically, depending on the configuration of the operating system.
  • Page 102: Starting Trovis-View And Performing Basic Settings

    Settings in TROVIS-VIEW software 15.3 Starting TROVIS-VIEW and performing basic settings You can perform the settings in TROVIS-VIEW either when the positioner is connected (on- line) to the computer or not connected (offline). Note: When the positioner is not connected, the default settings appear on the operator in- terface or, alternatively, a stored TROVIS-VIEW file (*.tro) can be loaded and overwritten by selecting Open in the File menu.
  • Page 103 5. Set the communications port for data communication. Proceed as follows: Connect the port (RS-232 or USB) of the computer using the corresponding adapter to the SAMSON SSP interface of the positioner. Select Communications in Options menu to open the server settings window. Click Server settings button.
  • Page 104: Data Transmission

    Settings in TROVIS-VIEW software Converting the software version The TROVIS-VIEW software version must match the firmware of the positioner. On exchanging data between the positioner and TROVIS-VIEW, the software automatically checks whether the versions are compatible and, if necessary, converts the data. If you want to adapt the firmware version without exchanging any data, proceed as follows: 1.
  • Page 105: Offline Operation (Indirect Data Transmission)

    Settings in TROVIS-VIEW software Note: Perform the electrical connection as described in section 5.2 first before downloading any data to the positioner. 15.4.1 Offline operation (indirect data transmission) In offline mode, there is no constant data communication between the computer and positioner.
  • Page 106: Setting Parameters

    Settings in TROVIS-VIEW software Operational data graphs (Trend Viewer) In online mode, process data (positioning value TRD, actual valve position and set point deviation [e]) are plotted in a graph over time. Select Trend Viewer in the View menu. You can modify the graphs, for example, by adding data points that should be recorded, or even remove data points.
  • Page 107 Settings in TROVIS-VIEW software 1. Click on one of the folders in the left tree directory to view the parameter settings on the right. Place the cursor over a data point to open a tool tip providing more information on the parameter.
  • Page 108: Initializing The Positioner

    Settings in TROVIS-VIEW software 15.5 Initializing the positioner Initializing the positioner is only possible in TROVIS-VIEW when the positioner has been at- tached properly to the control valve and has been connected (see sections 4 and 5). The positioner must be connected to the computer over the serial interface adapter. NOTICE During the initialization, the control valve moves through its entire travel/angle of rotation range.
  • Page 109 Settings in TROVIS-VIEW software 3. Start initialization by right-clicking Initialization and selecting Execute . How long the initialization procedure lasts depends on the actuator transit time and may take a few minutes. EB 8384-2 EN...
  • Page 110: Status Classification

    Settings in TROVIS-VIEW software 15.6 Status classification Messages are classified in the positioner with a status when an error occurs. States include “Maintenance alarm“, “Maintenance required“, “Maintenance demanded “, “Out of specifi- cation“ and “No message“. Maintenance alarm The positioner cannot perform its control task due to a functional fault in the device or in one of its peripherals or an initialization has not yet been successfully completed.
  • Page 111 Settings in TROVIS-VIEW software To provide a better overview, the classified messages are summarized in a condensed state which is made up from a summary of all classified positioner messages. The condensed state appears in TROVIS-VIEW3 on the right-hand side of the info bar and in the Diagnosis folder (>...
  • Page 112: Dimensions In Mm

    Dimensions in mm Dimensions in mm Pressure gauge External Attachment acc. to IEC 60534-6 or connecting plate bracket position sensor Lever mm S = 17 M = 50 L = 100 XL = 200 Direct attachment M20 x 1.5 Output (38) Supply (9) Fig.
  • Page 113 Dimensions in mm Heavy-duty version Output Y Output Y Supply (9) Output Y Output Y Reversing amplifier (optional)* Ø 101 Light version Output A1 Supply (9) Reversing amplifier Output A2 (optional)* Connecting * Reversing amplifier plate G ¼ or ¼ NPT –...
  • Page 114: Fixing Levels According To Vdi/Vde 3845 (September 2010)

    Dimensions in mm 16.1 Fixing levels according to VDI/VDE 3845 (September 2010) Level 2 (bracket surface) Level 1 (actuator surface) Actuator Dimensions in mm Size Æd ÆD* 5.5 for M5 5.5 for M5 5.5 for M5 ØD 5.5 for M5 5.5 for M5 6.5 for M6 * Flange type F05 according to DIN EN ISO 5211...
  • Page 115: Valve Characteristic Selection

    Valve characteristic selection Valve characteristic selection The characteristics that can be selected in Code 20 are shown in following in graph form. Note: A characteristic can only be defined (user-defined characteristic) using a workstation/ operating software (e.g. TROVIS-VIEW). Linear (select characteristic: 0) Travel/ angle of rotation [%] Reference variable [%] Equal percentage (select characteristic: 1)
  • Page 116 SAMSON butterfly valve linear SAMSON butterfly valve equal percentage (select characteristic: 3) (select characteristic: 4) Travel/ angle of rotation [%] Travel/ angle of rotation [%] Reference variable [%] Reference variable [%] VETEC rotary plug valve linear VETEC rotary plug valve equal percentage...
  • Page 117: Test Certificates

    EB 8384-2 EN...
  • Page 118 EB 8384-2 EN...
  • Page 119 EB 8384-2 EN...
  • Page 120 EB 8384-2 EN...
  • Page 121 EB 8384-2 EN...
  • Page 122 EB 8384-2 EN...
  • Page 123 EB 8384-2 EN...
  • Page 124 EB 8384-2 EN...
  • Page 125 EB 8384-2 EN...
  • Page 126 EB 8384-2 EN...
  • Page 127 EB 8384-2 EN...
  • Page 128 EB 8384-2 EN...
  • Page 129 EB 8384-2 EN...
  • Page 130 EB 8384-2 EN...
  • Page 131 EB 8384-2 EN...
  • Page 132 EB 8384-2 EN...
  • Page 133 EB 8384-2 EN...
  • Page 134 EB 8384-2 EN...
  • Page 135 EB 8384-2 EN...
  • Page 136 EB 8384-2 EN...
  • Page 137 EB 8384-2 EN...
  • Page 138 EB 8384-2 EN...
  • Page 139 EB 8384-2 EN...
  • Page 140 SAMSON AG · MESS- UND REGELTECHNIK Weismüllerstraße 3 · 60314 Frankfurt am Main · Germany Phone: +49 69 4009-0 · Fax: +49 69 4009-1507 EB 8384-2 EN Internet: http://www.samson.de...

This manual is also suitable for:

3730-23730 series3730-2 series

Table of Contents

Save PDF