5 Repair
5.7 Replacement of the transformer
Continued
16
17
18
19
20
Continues on next page
98
Action
Reuse the secondary leaders.
Clean the contact surfaces with a clean
cloth. Use scotch brite (very fine grade)
if necessary.
Lubricate the contact surfaces with con-
tact paste.
Spread the paste evenly over the entire
contact surfaces using a brush.
Reassemble the screws (pos. 1) holding
the secondary leaders (pos. 2).
Tighten by hand.
Reuse the water couplings from the old
transformer by reassembling the coup-
lings on the new transformer.
Apply thread sealant before assemble.
Note
If the water couplings are damaged, re-
place with new ones.
Reassemble the transformer (pos. 1) with
the mounting screws (pos. 2), two on
each side.
Use standard tightening torque according
to
Bolt, screws, tightening torques on
page
118.