Palm Led Is Steady On; Lpu Failures; Run Led Is Off - H3C SR6600-X Series Manual

Hide thumbs Also See for SR6600-X Series:
Table of Contents

Advertisement

PALM LED is steady on

Symptom
The PALM LED for the MPU is steady on. For more information about MPU LEDs, see Table7-1.
Solution
To resolve the problem:
1.
Verify that the power supply and power consumption match.
For example, if an SR6616-X is installed with a 650 W power module but two SAP-48GBE
modules, the power available is not sufficient for the whole power consumption and one SAP
module cannot be powered on.
2.
Verify that the router has one type of power modules installed: AC power modules or DC power
modules.
3.
If the problem persists, contact H3C Support.
Table7-1 MPU LEDs
LED
RUN (green)
ACT (green)
PALM (red)
ALM (red)

LPU failures

RUN LED is off

Symptom
The RUN LED for the LPU is off.
Solution
To resolve the problem:
1.
Verify that the router is powered on.
2.
Verify that the LPU is correctly inserted in a slot.
Status
Off
Flashing slowly at 1 Hz
Flashing fast at 8 Hz
Off
Steady on
Off
Steady on
Off
Steady on
Flashing fast at 8 Hz
Description
No power is provided or the MPU is faulty.
The MPU is operating correctly.
The MPU is loading system software images. To avoid MPU
damage, do not power off the router or hot-swap the MPU.
The MPU is not operating.
The MPU is in standby state.
The MPU is in active state.
The power supply is operating correctly.
The power for use is not sufficient, or power modules of different
specifications are inserted.
The system is operating correctly without any alarm.
The system is faulty. You must view the system logs.
The system is seriously faulty. An immediate action is needed.
70