21 - COMMUNICATION

21.1 - COMMUNICATION/RS232

The ADL300 drive is provided with a standard port (9 pole sub-D connector: XS) for connecting the RS232 serial line used for drive-
PC point-to-point communication (via the GF-eXpress configuration software).
Menu
PAR
Description
21.1.1
3800 Drive address
Setting of the address to which the drive responds when connected to the RS232 serial line.
Menu
PAR
Description
21.1.2
3802 Serial baudrate
Setting of the RS232 serial communication speed (Baud Rate).
0
9600
1
19200
2
38400
Menu
PAR
Description
21.1.3
3810 Serial parameter
Setting of the format of the RS232 serial line.
0
None,8,1
1
None,8,2
2
Even,8,1
3
Odd,8,1
Menu
PAR
Description
21.1.4
3804 Serial protocol
Setting of the serial communication protocol:
0
Modbus
1
Jbus
Setting to 0 selects the Modbus RTU (Remote Terminal Unit) serial communication protocol.
Setting to 1 selects the Jbus serial communication protocol. The Jbus protocol is functionally identical to the Modbus, ex-
cept for the different numbering of addresses: in the Modbus these start from zero (0000 = 1st address) while in the JBUS
they start from one (0001 = 1st address) and maintain this difference throughout numbering.
Menu
PAR
Description
21.1.5
3806 Serial delay
Setting of the minimum delay between the drive receiving the last byte and starting its response. This delay avoids conflicts
on the serial line when the RS232 interface that is used has not been pre-set for automatic Tx/Rx switching. The parameter
only concerns the use of the standard RS232 serial line.
Example: if the delay in Tx/Rx switching on the master is a maximum of 20ms, the Ser answer delay parameter must be
set to at least 20ms: 22ms
Menu
PAR
Description
21.1.6
3808 Serial swap data
This parameter enables the exchange of the reading of the High and Low parts of the words for FLOAT type parameters
when using the Modbus protocol.

21.2 - COMMUNICATION/FIELDBUS CONFIG

Menu
PAR
Description
21.2.1
4000 Fieldbus type
Setting of the type of fieldbus to be used.
0
Off
1
CANopen
10
DS417
If set to 0 no fieldbus is selected.
If set to 1 the CANopen fieldbus profile is selected.
If set to 10 the DS417 fieldbus is selected.
94
UM
Type
FB BIT
UINT16
UM
Type
FB BIT
ENUM
UM
Type
FB BIT
ENUM
UM
Type
FB BIT
ENUM
UM
Type
FB BIT
ms
UINT16
UM
Type
FB BIT
BIT
UM
Type
FB BIT
ENUM
ADL300 • Functions description and parameters list
Def
Min
1
1
Def
Min
38400
0
Def
Min
None,8,1
0
Def
Min
Modbus
0
Def
Min
0
0
Def
Min
0
0
Def
Min
Spento
0
Max
Acc
Mod
255
ERW
FVS
Max
Acc
Mod
2
ERW
FVS
Max
Acc
Mod
3
ERW
FVS
Max
Acc
Mod
1
ERW
FVS
Max
Acc
Mod
1000
ERW
FVS
Max
Acc
Mod
1
ERW
FVS
Max
Acc
Mod
2
ERW
FVS