gefran SIEIDrive ADL300 Functions Description And Parameters List page 25

Vector inverter for lifts with asynchronous motors
Hide thumbs Also See for SIEIDrive ADL300:
Table of Contents

Advertisement

Setting of the door opening speed.
Source to enable brake release through the digital input. In standard sequence brake release is controlled
by the drive and therefore this parameter is set to ONE. In case that brake release should be conditioned
by some external control (e.g. PLC), set this parameter to digital input controlled by PLC.
Internal sequence for brake release will wait until this input is asserted.
During run brake will be closed whenever this input becomes not asserted.
Menu
PAR
Description
5.3.13 11088 Contactorless Enable
This should be configured if the contactorless mode is desired. By enabling this parameter, the fast enable command is
brought to digital Input 7 and the drive indicates the contactorless operation mode to the controller through digital output 4
(see Figure 7.3.2.8-A in the ADL300 QS installation manual).
Menu
PAR
Description
5.3.14
11826 Inspection Behaviour
0
None
1
Fast Stop
2
Immediate
Manages the stop ramp in maintenance/inspection mode. If enabled, the function allows greater deceleration compared to
nominal deceleration.
Three modes are available:
None:
Fast Stop:
Immediate: car stops immediately with brake close. The car stops immediately (with no ramp) when the button on the
Menu
PAR
Description
5.3.15
11828 Inspection speed
0
Multi speed 0
1
Multi speed 1
2
Multi speed 2
3
Multi speed 3
4
Multi speed 4
5
Multi speed 5
6
Multi speed 6
7
Multi speed 7
8
Null
Maintenance speed.
Menu
PAR
Description
5.3.16
12014 Trip number
The lift journey counter is displayed. The counter increases each time the Start lift signal is activated.
Menu
PAR
Description
5.3.17
12016 Sequence state
The lift sequence status is displayed.
Ref
PAR 12016 description
0
Idle
1
Cont close
2
Drive ready
Door open src
Speed
UM
Type
UM
Type
Enum
function disabled (default). The car stops with the normal ramps inserted.
the 200 ms stop function is enabled if the set maintenance speed (PAR 11024 Multi speed 2 or PAR 11828
Inspection speed) is below 0.63 m/s. If the set speed is higher it is automatically limited to 0.63 m/s.
maintenance button panel is released.
UM
Type
Enum
UM
Type
INT32
UM
Type
UINT16
Note
Not active
Close Contact on Sequence lift diagram (*)
ADL300 • Functions description and parameters list
Door open speed
FB BIT
Def
BIT
0
FB BIT
Def
None
FB BIT
Def
2
FB BIT
Def
0
FB BIT
Def
0
Function enable signal
Min
Max
0
1
Min
Max
0
2
Min
Max
Min
Max
Min
Max
Acc
Mod
RW
FVS
Acc
Mod
R/Z
FVS
Acc
Mod
R/Z
FVS
Acc
Mod
R
FVS
Acc
Mod
R
FVS