Alarm
Bres ovld
InAir
PhLoss
Opt Bus
Mot PhLoss
Menu
PAR
Description
22.1
4500 Fault reset src
Selection of the origin (source) of the signal to be used for the command to reset the drive after an alarm. The terminal that
can be used for this function can be selected from among those listed in the "L_DIGSEL2" selection list.
Menu
PAR
Description
22.2
4502 ExtFlt src
Selection of the origin (source) of the signal to be used as the input for the drive external fault alarm ExtFlt. The terminal
that can be used for this function can be selected from among those listed in the "L_DIGSEL2" selection list.
Menu
PAR
Description
22.3
4504 ExtFlt activity
Setting of the behaviour of the drive in the event of an external fault alarm ExtFlt. This alarm indicates the intervention of a
drive external protection.
0
Ignore
1
Warning
2
Disable
3
Stop
4
Fast stop
Menu
PAR
Description
22.4
4506 ExtFlt restart
Enabling of automatic restart after the external fault alarm ExtFlt
0
Disable
1
Enable
Menu
PAR
Description
22.5
4508 ExtFlt restart time
Setting of the time within which the External Fault alarm must be reset in order to perform automatic restart.
Menu
PAR
Description
22.6
4510 ExtFlt holdoff
Setting of the delay between the signalling of the external fault alarm ExtFlt and enabling of the alarm. If an alarm condi-
tion occurs, the drive will wait for the set time before blocking is enabled. If the alarm is removed within the set time, the
drive will not indicate any alarm condition.
Menu
PAR
Description
22.7
4520 MotorOT src
Selection of the origin (source) of the signal to be used for the motor overtemperature alarm MotorOT. The terminal that
can be used for this function can be selected from among those listed in the "L_DIGSEL2" selection list".
Menu
PAR
Description
22.8
4522 MotorOT activity
Setting of the behaviour of the drive in case of a motor overtemperature alarm MotorOT. This alarm indicates that the mo-
tor temperature is too high.
0
Ignore
1
Warning
2
Disable
3
Stop
Ignore
Warning
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
UM
Type
FB BIT
LINK
16BIT
UM
Type
FB BIT
LINK
16BIT
UM
Type
FB BIT
ENUM
UM
Type
FB BIT
ENUM
UM
Type
FB BIT
ms
UINT16
UM
Type
FB BIT
ms
UINT16
UM
Type
FB BIT
LINK
16BIT
UM
Type
FB BIT
ENUM
ADL300 • Functions description and parameters list
Disable drive
Stop
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
Def
Min
6000
0
Def
Min
6000
0
Def
Min
Disable
0
Def
Min
Disable
0
Def
Min
1000
120
Def
Min
0
0
Def
Min
6000
0
Def
Min
Warning
0
Fast stop
ü
ü
ü
ü
ü
Max
Acc
Mod
16384
RW
FVS
Max
Acc
Mod
16384
RW
FVS
Max
Acc
Mod
4
RW
FVS
Max
Acc
Mod
1
RW
FVS
Max
Acc
Mod
30000
RW
FVS
Max
Acc
Mod
10000
RW
FVS
Max
Acc
Mod
16384
RW
FVS
Max
Acc
Mod
4
RW
FVS
103