Advertisement

5.3 – LIFT SEQUENCES
This menu shows the parameters used to manage and define the travel of the lift depending on the status of the inputs and alarms.
The structure of the lift sequences is summarised below.
Lift DC brake mon
Starting sequence:
1
Reading of the enable hardware input and checking for alarms (enabling is aborted in case of an alarm)
2
Detection of the Enable and Start commands as set in the Sequence start mode parameter
When the Start forward/reverse command is received, a command is sent to close the contactors, depending on the
3
direction of travel
4
When the time set in Cont close delay has elapsed the internal Enable lift signal is activated
5
The system waits for the magnetisation signal from the drive (Drive ready)
6
At the end of magnetisation the open brake signal is activated
22
HW Enable
Start / Rev cmd
Mlt spd s 0
Mlt spd s 1
Mlt spd s 2
Acc ini jerk
Speed ref 1
Magn. current
Run Cont Close delay
RUN cont
Lift enable
cmd mon
Contactorless OK
BRAKE cont mon
Lift Start mon
Lift Landing mon
K2M/K3M delay of the contactors
K4 delay
Contactorless
enable
K2M / K3M
K4
ADL300 • Functions description and parameters list
Acc end jerk
Acceleration
Slow Down dist
Brake open delay
(Only FOC/BRS)
(Only V/F)
Running
Dec ini jerk
Deceleration
Dec end jerk
End decel
Spd 0 ref thr
Spd 0 ref delay
Run Cont open delay
Brake close dly
K4 delay
K2M/K3M delay