Motor Connection; Connection Of The Temperature Monitoring - KEB Combivert F5 series Installation Manual

5.5...7.5kw 230v 4.0...15kw 400v
Hide thumbs Also See for Combivert F5 series:
Table of Contents

Advertisement

Installation and Connection
3.3.4

Motor connection

Maximum motor line length see chapter 2.3
Motor-PTC
(optionally)
3.3.5

Connection of the temperature monitoring

• Terminals T1, T2
• Tripping resistance 1.65...4 kΩ
• Reset resistance 0.75...1.65 kΩ
• Design in accordance with VDE 0660 Part 302
• This function can be activated by the machine builder by software
• Do not lay connecting cable together with control cable
• Permissible in the motor cable only with double shielding
• Connect relay K1 for fire prevention in regenerative operation (see 3.3.6)
K1
12
GB - 12
M
3~
PE
U
V
W
Other
11
Apply shieldings over a large
contact surface of the mounting
plate
Motor-PTC
X1A
L1
N/L2
L3
++
--
PB
U
V
W
T1
T2
T1
T2