Figure 27: Connection Of The Brake Control; Figure 28: Connection Of A Kty Sensor - KEB COMBIVERT F6 Series Instructions For Use Manual

Installation f6 housing 2 peak power standard ol-function
Hide thumbs Also See for COMBIVERT F6 Series:
Table of Contents

Advertisement

CONNECTION OF THE POWER UNIT
1
X1C
2
1
COMBIVERT
4
Brake
Figure 27:
Connection of the brake control
TA1
+
KTY84
TA2
1
Connection via shield plate (if not available, place on the mounting plate).
Figure 28:
Connection of a KTY sensor
NOTICE
For control board APPLICATION and COMPACT.
The voltage to the control of a brake is decoupled from the
internal voltage supply. The brake works only with external
voltage supply.
= 24V
U
_dc
For control board PRO
= 2A
I
_max
The brake can be supplied with both, internal and external
voltage. Voltage tolerances and output currents vary for
internal and external voltage supply..
Respect the specifications
=>
instruction manual „control board"
KTY sensors are polarized semiconductors and must be
operated in forward direction!
To this connect the anode to TA1 and the cathode to TA2!
Non-observance leads to incorrect measurements in the
upper temperature range. A protection of the motor win-
ding is then no longer guaranteed.
No protection of the motor winding in case of wrong connection.
► Operate KTY sensors in forward direction.
► KTY sensors may not be combined with other detections.
Further information about the wiring of the temperature monitoring and the
brake control have to be observed in the respective control unit manual.