DEVICE DATA OF THE PEAK POWER DEVICES
The following characteristic curve indicates the permissible maximum current for the out-
put frequency values 0 Hz, 3.1 Hz, 6.2 Hz, 12.5 Hz, 25 Hz and 50 Hz. Device size 16 is
represented exemplary.
260
240
220
200
180
160
140
120
100
80
60
40
20
0
0
5
Legend
Overcurrent I
OC
Software current limit I
Switching frequency 2 kHz
Switching frequency 4 kHz
Switching frequency 8 kHz
Not available for modulation. Error OC is triggered at 230% overload.
Figure 4:
Typical overload characteristics in the lower output frequencies (OL2) example device size 16
36
10
15
20
25
Output frequency / Hz
(the limit can be set with parameter is35)
lim
The frequency-dependent maximum current I
output current I
.
N
The current remains constant from the last specified output frequency value.
30
35
40
45
out_max
50
55
60
refers in % to the rated