Use Of Intrinsically Safe Braking Resistors; Use Of Non-Intrinsically Safe Braking Resistors; Figure 30: Wiring Of An Intrinsically Safe Braking Resistor - KEB COMBIVERT F6 Series Instructions For Use Manual

Installation f6 housing 2 peak power standard ol-function
Hide thumbs Also See for COMBIVERT F6 Series:
Table of Contents

Advertisement

CONNECTION OF THE POWER UNIT

5.2.6.2 Use of intrinsically safe braking resistors

Legend
1
2
Figure 30:

5.2.6.3 Use of non-intrinsically safe braking resistors

WARNING
68
Twist the connection cable. When extending the connection cables, the cables
must be shielded additionally and connected on both sides.
Protective earthing is provided via the housing.
Wiring of an intrinsically safe braking resistor
Intrinsically safe braking resisitors behave in error case
such as a safety fuse. They interrupt themselves without
fire risk.
More information about intrinsically safe braking resistors
www.keb.de/fileadmin/media/Manuals/dr/ma_dr_safe-braking-
tors-20106652_en.pdf
Use of non-intrinsically safe braking resistors
Fire or smoke in case of overload or fault !
► Only use braking resistors with temperature sensor.
► Evaluate temperature sensor.
► Trigger a fault on the drive controller (e.g. external input).
► Switching off input voltage (e.g. input contactor).
► Connection examples for non-intrinsically safe braking resistors
► =>
Instructions for use "Installation braking resistors"
Instructions for use "Installation braking resistors"
www.keb.de/fileadmin/media/Manuals/dr/ma_dr_braking-
tors-20116737_en.pdf
X1A
R
- -
++
resis-
resis-