CONNECTION OF THE POWER UNIT
5.2.6.2 Use of intrinsically safe braking resistors
Legend
1
2
Figure 30:
5.2.6.3 Use of non-intrinsically safe braking resistors
WARNING
68
②
Twist the connection cable. When extending the connection cables, the cables
must be shielded additionally and connected on both sides.
Protective earthing is provided via the housing.
Wiring of an intrinsically safe braking resistor
Intrinsically safe braking resisitors behave in error case
such as a safety fuse. They interrupt themselves without
fire risk.
More information about intrinsically safe braking resistors
www.keb.de/fileadmin/media/Manuals/dr/ma_dr_safe-braking-
tors-20106652_en.pdf
Use of non-intrinsically safe braking resistors
Fire or smoke in case of overload or fault !
► Only use braking resistors with temperature sensor.
► Evaluate temperature sensor.
► Trigger a fault on the drive controller (e.g. external input).
► Switching off input voltage (e.g. input contactor).
► Connection examples for non-intrinsically safe braking resistors
► =>
Instructions for use "Installation braking resistors"
Instructions for use "Installation braking resistors"
www.keb.de/fileadmin/media/Manuals/dr/ma_dr_braking-
tors-20116737_en.pdf
X1A
①
R
- -
++
resis-
resis-