pump type is set to Demand and if the differential be-
tween Oil Pressure and Suction Pressure is less than
50 PSI for 5 seconds this shutdown will occur. This
shutdown is only active when the compressor is run-
ning and is also not checked for the fi rst 90 seconds
after the compressor starts.
Low Oil Differential 2 (Kobe) – If the compressor
type is set to Other Manufacturer (Kobe), the oil
pump type is set to Demand and the differential be-
tween Oil Pressure and Suction Pressure is less than
Suction Pressure times 0.8 for 5 seconds this shut-
down will occur. This shutdown is only active when
the compressor is running and is also not checked for
the fi rst 90 seconds after the compressor starts.
Low Oil Separator Temp Sensor Warning - This
warning message is issued if the Oil Separator Tem-
perature reading (analog board 1, channel 4) was to
the lower or minimum range (out of range) for its
sensor.
Low Oil Temp Compressor Sensor Warning - This
warning message is issued if the Oil Temperature
reading (analog board 1, channel 3) was to the lower
or minimum range (out of range) for its sensor.
Low Process Entering Temp Sensor Warning - This
warning message is issued if the Process Entering
Temperature reading (analog board 2, channel 4) was
to the lower or minimum range (out of range) for its
sensor.
Low Process Entering Temp Shutdown - The En-
tering Process Temperature was less than or equal
to the Low Entering Process Temperature Shutdown
setpoint for its time delay.
Low Process Entering Temp Warning - The Entering
Process Temperature was less than or equal to the
Low Entering Process Temperature Warning setpoint
for its time delay.
Low Process Leaving Temp Sensor Warning - This
warning message is issued if the Process Leaving
Temperature reading (analog board 1, channel 5) was
to the lower or minimum range (out of range) for its
sensor.
Low Process Leaving Temp Shutdown - The Leaving
Process Temperature was less than or equal to the
Low Leaving Process Temperature Shutdown setpoint
for its time delay.
Low Process Leaving Temp Warning - The Leaving
Process Temperature was less than or equal to the
Low Leaving Process Temperature Warning setpoint
for its time delay.
Low Rem Capacity Position Sensor Warning - This
warning message is issued if the Remote Capacity
Position reading was to the lower or minimum range
(out of range) for its sensor.
QUANTUM™ LX COMPRESSOR CONTROL PANEL
OPERATION
Low Remote Control Setpoint Sensor Warning –
Low RPM Sensor Warning - This warning message
is issued if the RPM reading was to the lower or mini-
mum range (out of range) for its sensor.
Low RPM Shutdown - This shutdown applies if En-
gine or Turbine Drive was enabled. If the RPM's of
the motor drops below this setpoint, a shutdown will
occur. To access this setpoint: Menu > Setpoints >
Engine.
Low RPM Warning - This warning applies if Engine
or Turbine Drive was enabled. If the RPM's of the mo-
tor drops below this setpoint, a warning will occur.
To access this setpoint: Menu > Setpoints > Engine.
Low Separator Temperature Sensor Fault - This
shutdown message is issued if the Separator Tem-
perature reading was to the lower or minimum range
(out of range) for its sensor.
Low Separator Temperature Shutdown - The Oil
Separator Temperature was less than or equal to the
Low Oil Separator Temperature Shutdown setpoint
for its time delay. To access this setpoint: Menu >
Setpoints > Package.
Low Separator Temperature Warning - The Oil
Separator Temperature was less than or equal to the
Low Oil Separator Temperature Warning setpoint for
its time delay. To access this setpoint: Menu > Set-
points > Package.
Low Suction Pressure Sensor Fault - This shutdown
message is issued if the Suction Pressure reading was
to the lower or minimum range (out of range) for its
sensor.
Low Suction Shutdown -- Mode 1 - When running
in Mode 1, if the Suction Pressure was less than or
equal to the active Mode 1 Low Suction Shutdown
setpoint for its time delay.
Low Suction Shutdown -- Mode 2 - When running
in Mode 2, if the Suction Pressure was less than or
equal to the active Mode 2 Low Suction Shutdown
setpoint for its time delay.
Low Suction Shutdown -- Mode 3 - When running
in Mode 3, if the Suction Pressure was less than or
equal to the active Mode 3 Low Suction Shutdown
setpoint for its time delay.
Low Suction Shutdown –- Mode 4 - When running
in Mode 4, if the Suction Pressure was less than or
equal to the active Mode 4 Low Suction Shutdown
setpoint for its time delay.
Low Suction Pressure Sensor Warning - This warn-
ing message is issued if the Suction Pressure reading
(analog board 1, channel 1) was to the lower or mini-
mum range (out of range) for its sensor.