Page 2
(especially in bedrooms), smoking in bed, and violent explosions (caused by escaping gas, improper storage of Limit-C1-2-2007 flammable materials, etc.). Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
Page 4
•Your suggestion for how to correct/improve documentation Send email messages to: FireSystems.TechPubs@honeywell.com Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical Services. Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
IFC-3030/IFC2-3030 • JNCA and JNCA-2 This document also provides basic information that applies to Johnson Controls SLC loops in general, such as the branch resistance measurements. See Section 2.4, “Control Panel Terminal Blocks”, on page 20 for basic panel-end SLC connections.
51304 AMPS-24/E Power Supply Manual 51907 FCPS-24 Field Charger/Power Supply Manual 50059 Field Charger/Power Supply FCPS-24 Technical Bulletin LIT-445111 Table 1.1 Reference Documentation (1 of 3) Continued on next page... Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
Page 10
1351J Ion Detector Installation Document I56-1362 1951J Ion Detector Installation Document I56-1929 7351J VIEW® Laser Detector Installation Document I56-1898 2351J & 2351TJ Photo Installation Document I56-1366 Table 1.1 Reference Documentation (2 of 3) Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
Protocol Use: LCM-320/LEM-320 loops on IFC2-640, IFC-640/E and IFC-3030/IFC2-3030, and SLC loops on IFC-320 can run in FlashScan mode or CLIP mode. IFC-200, IFC-300/IFC-400, IFC-1010 and IFC-2020 run in CLIP mode only. Many FlashScan devices can be programmed to run in either CLIP or FlashScan mode. Use one of the following three options with SLC loops: Program all modules and detectors on an SLC as FlashScan.
SLC loop, allowing critical components to function in the event of a circuit fault. Isolator modules are required to meet the requirements of an NFPA Style 7 circuit. • M500XJ Loop Fault Isolator Module; FlashScan or CLIP mode. Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
JCI panels offer different feature sets across different models. Certain features of the 2951J-COPTIR may not be available on some panels. The 2951J-COPTIR supports both FlashScan and CLIP modes. Read Status limitations may apply in CLIP mode. Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
Supports FlashScan and CLIP mode; compatible with IFC-300/IFC-400, IFC-320, IFC2-640, IFC-640, and IFC-3030/IFC2-3030 only. LPX-751L is compatible with IFC-200 and IFC-1010/IFC-2020; CLIP mode only. (An earlier version named 7251J was CLIP mode only and compatible with IFC-300/IFC-400.) 1.6.8 Addressable Manual Pull Stations...
• Alarm - The control panel must be able to process an alarm input signal in the presence of this type of fault. Table 1.2 SLC Circuit Configuration and Performance: Style 4, Style 6, Style 7 Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
GREEN continuous IFC-3030, Detector Blinks RED RED continuous Blinks GREEN RED continuous IFC2-3030 NOTE: In CLIP mode, the 7251J and FTX-P1J blink GREEN in standby and stay RED when activated. Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
Note: Maximum total capacitance of all SLC wiring (both between conductors and from any conductor to ground) should not exceed 0.5 microfarads. Table 2.1 Wiring Recommendations: IFC-320, IFC2-640, IFC-640, IFC2-3030, IFC-3030, JLIB-200A, JLIB-400, LEM-320, and LCM-320 Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
With power removed, short the termination point of one branch at a time and measure the DC resistance from the beginning of the SLC to the end of that particular branch. Repeat this procedure for all remaining branches in the SLC. Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
Short the SLC at the first device and measure the resistance at SLC return. Record resistance and remove the short. The maximum DC resistance of the SLC is the higher of 2 and 3. Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
TB1 on the LCM-320 or LEM-320. SLC Loop Connections SLC Loop Connections on Loop Control Modules on Loop Expander Module Figure 2.5 IFC2-3030, IFC-3030 SLC Loop Connections and Wiring Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
Loop Expander Module Figure 2.7 SLC Loop Connections and Wiring 2.4.4 IFC-200 IFC-200 supports one SLC loop; the loop is CLIP mode only. The SLC loop connects to TB5. SLC Loop #1 Connections on FACP’s main circuit board Figure 2.8 SLC Connections for IFC-200...
Section 3: Shielded Wire Termination 3.1 Overview This section shows the proper termination of the shield, if used. Shielding of the SLC is recommended for use with IFC-200, IFC-300/400, JLIB-200. Proper termination of the shield depends on the type of conduit used: •...
Do not allow the shield drain wire to enter the system cabinet or the conduit. Foil Shield Drain Wire Cabinet Conduit Figure 3.3 Shield Termination – Partial Conduit Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
NOTE: Using shielded wire in applications where it is not recommended will reduce the maximum SLC length. If shielded wire must be used where not recommended, failing to float the ends will reduce the maximum SLC length even further. Figure 3.4 Floating the Shield Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
Addressable Module SLC Return B+ B– A– A+ Control Panel NOTE: T-tapping of the SLC wiring is NOT allowed for Style 6 configuration. Figure 4.2 Basic NFPA Style 6 SLC Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
5.2.1 Wiring an Isolator Module Figure 5.1 shows a Style 4 example for wiring of an Isolator Module. Continuation of the SLC Isolated branch of the SLC Figure 5.1 Wiring the M500XJ Module Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
Short-circuit path NOTE: For information on wiring an isolator base, refer to Figure 9.3, “Wiring an Isolator Base” on page 50. Figure 5.2 Isolator Base Circuit: Sample Style 6 Wiring Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
FACP, or these isolator Control Panel modules must be connected within 20 ft. (6.1 m) of the FACP enclosure in conduit. Figure 5.4 NFPA Style 6 SLC Using Isolator Modules Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
20 ft. (6.1 m) of the FACP enclosure in conduit. Control Panel NOTE: See Figure 9.3, “Wiring an Isolator Base” on page 50. Figure 5.5 NFPA Style 7 SLC Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
Rotary IDC Return – SLC+ Switches IDC Return + IDC Out + IDC Out – Areas used to record the device address and SLC number. Figure 6.2 M302MJ Zone-interface Module Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
T9 is only used in three-wire sensor applications. For two- wire applications, T8 is used for negative (-) wiring. Area used to record the device address and SLC number. Figure 6.5 M300MJ-4-20 4-20mA Monitor Module Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
Dual monitor modules: On dual monitor modules, only even numbers appear on the ONES rotary switch. The module takes both the selected address and the next-higher address. Figure 6.6 Setting SLC Address on Module Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
24 VDC Power Detector Base Filtered, Regulated, Resettable Manual pull station To Next IDC 47K ELR Supervision Device (supplied with module) Heat detector Figure 6.7 Typical Style B IDC Wiring with M300MJ Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
24 VDC Four-wire 24 VDC Power Detector Base Filtered, Regulated, Resettable Manual pull station To Next IDC Supervision Device Heat detector Figure 6.8 Typical Style D IDC Wiring with M300MJ Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
Refer to the Device Compatibility Document for compatible smoke detectors. Manual Pull Station Heat Detector M300DJ Base +1 Address Base Address (IDC Circuit H) (IDC Circuit L) Figure 6.9 Typical Style B IDC Wiring with M300DJ Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
(Non-resettable power may be used for IFC- 320/E/C, IFC2-640/E, IFC-640/E, IFC2-3030, Two-wire or IFC-3030 when operating in FlashScan smoke mode.) detectors 3.9K ELR (supplied with module) M302MJ Figure 6.10 Typical Style B IDC Wiring with M302MJ Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
IFC-320/E/C, IFC2-640/E, IFC-640/E, Two-wire IFC2-3030, or IFC-3030 when operating in smoke FlashScan mode.) detectors M302MJ 3.9K ELR (supplied with module) Figure 6.11 Typical Style D IDC Wiring with the M302MJ Figure 6.12 Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
(70.7 VRMS max audio or telephone); refer to the Voice Alarm System Manual, FireVoice 25/50 Manual or DVC Manual as appropriate for your equipment. Figure 7.1 M300CJ Wiring Connections Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
Rear View - Jumper Location Wiring Connections Figure 7.3 M300CJ-REL Wiring Connections and Rear View - Jumper Location NOTE: The M300CJ-REL will not function on an SLC loop that is programmed for CLIP mode. Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
47K, 1/2-watt Appliances FlashScan type IDs that provide built-in power supervision, no relay is required.) Module polarities are shown in alarm condition Figure 7.4 NFPA Style Y Notification Appliance Circuit Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
If using one of the’s FlashScan type IDs that provide built-in power supervision, no relay is Module polarities are shown in Alarm. required.) Figure 7.5 NFPA Style Z Notification Appliance Circuit Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
Do not T-tap or branch a Style Y or Style Z circuit. Only one (1) 24V solenoid or two (2) 12V solenoids in series can be connected to the M300CJ- REL. Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
Page 46
Refer to your FACP’s Programming Manual for instructions on setting the Soak Timer. The M300CJ-REL module must be programmed with the correct releasing type code listed in your FACP’s Programming Manual. Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
Section 6.2, “Setting an SLC Address for a Module”, on page 35. 8.2 Wiring the Addressable Relay Module (Form-C Relay) The figure below shows the M300RJ module wired to the Control Panel. Figure 8.1 Relay Module Wiring Connections Figure 8.2 Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
RA400Z Remote LED Annunciator (Optional) NOTE: The B210LPJ base wiring is identical to the B501J, except there is no shield terminal. Figure 9.1 Wiring of the B501J Detector Base Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
Page 49
Power Supply RA400Z Remote LED Annunciator (Optional) NOTE: Use a spade lug to wire the Remote LED Annunciator (–) to Terminal 2 (–). Figure 9.2 Wiring of the B501B-FTXJ Detector Base Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
Figure 9.4 shows typical wiring of the B224RB plug-in relay detector base connected to an SLC. To next device on SLC For connection of cable shield Figure 9.4 Wiring of the B224RB Plug-in Relay Detector Base Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
External (+) Power Supply UL-listed Class A Optional Wiring EOL Relay *Grouping of up to 6 model B501BHT temporal tone sounder bases. Figure 9.5 Wiring of the B501BH/B501BHT Sounder Bases Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
10.2 Wiring a Manual Pull Station Typical wiring for the JBG-12LX Manual Pull Station to an SLC. – To next device on SLC – Figure 10.1 Wiring the JBG-12LX Pull Station to an SLC Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
= number of Notification Appliance Devices = Notification Appliance current when activated NOTE: This simplified equation assumes that the devices are at the end of a long wire run. The minimum supply voltages produced by Johnson Controls power supplies are listed below: FACP Power Supply IFC-200 19.4...
Last device on the SLC loop (M300CJ or M302MJ) Power Supervision Relay (EOLR-1) Supervised NAC or IDC (Use 47K with M300CJ or 3.9K with M302MJ) Figure A.1 Supervised 24 VDC Circuit Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
Page 55
Control Panel or Power Supply M300CJ ELR 47K Power Supervision Relay (EOLR-1) Supervised NAC or IDC ELR 47K M300MJ Figure A.2 Alternate: 2-Address Method of Supervising a 24 VDC Circuit Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
NAC Terminal Block (24 VDC) M300CJ Circuit supervised by control panel M300CJ Note: Drawing shows power wiring only; SLC Wiring not shown. Figure A.3 NFPA Style Y NAC Power (Alternate) Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
Page 57
NAC Terminal Block (24 VDC) M300CJ Circuit supervised by control panel M300CJ Note: Drawing shows power wiring only; SLC Wiring not shown. Figure A.4 NFPA Style Z NAC Power (Alternate) Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
Wiring connected to the surge suppressor output must remain within the building while wiring connected to the surge suppressor input may be routed outside the building as shown below. Building #2 Building #1 FACP P = Primary S = Secondary Surge Suppressor Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
NOTE: Use 12 AWG (3.31 mm ) to 18 AWG (0.82 mm ) wire with crimp-on connectors to connect the unit’s ground terminal to equipment ground. Wire length must be minimized to provide best protection Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
) wire with crimp-on connectors to connect the unit’s ground terminal to equipment ground. Wire length must be minimized to provide best protection. Do not connect shield (if present) to surge protector or fire panel. Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
SLC - SLC + Unused Normally Open (1) Normally Closed (1) Relay Common (1) Normally Open (2) Normally Closed (2) Relay Common (2) Unused Unused Table C.1 M300RJ Terminal Conversions Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
Page 64
SLC - SLC + VDC - VDC + Unused Solenoid B/A - Solenoid B/A + Solenoid A + Solenoid A - Unused Unused Table C.2 M300CJ and M302MJ Terminal Conversions Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
Page 65
SLC - SLC + Unused Unused Unused Class A/B Supervision - Class A/B Supervision + Class A Supervision + Class A Supervision - Unused Unused Table C.3 M300MJ Terminal Conversions Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
Page 66
M300MJA such as manual pull stations, four-wire smoke detectors, heat detectors, waterflow, and supervisory devices M302MJ M302MJA Used to interface with two-wire smoke detectors in addition to normally open contacts Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
Page 67
Controls six Form-C relays. XP10-M Supervises ten Class-B addressable Initiating Device XP10-MA Circuits (IDC) which monitor normally open contact initiating devices. XP6-MA Monitors six zones of conventional two-wire detectors. XP6-MAA Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
Page 68
60 communications loop 29 group poll 11 – conduit, types of 23 grouped fashion 11 connector screw 23 connectors, crimp-on 60 control modules 12 HARSH™ 49 Control Modules (Overview) 67 Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
Page 69
M300MJ 37 M300MJ, see monitor module 33 M300MJ-4-20 12 Terminal Designations 34 Output relays M300RJ, see Relay modules Connections 67 M301MJ, see miniature monitor module M302MJ, see zone interface module Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
Page 70
13 Style 4, Style 6, Style 7, Style B, Style D, Style Y, Style Z see NFPA Style 26 supervised circuits 54 supervised devices 54 suppressors, surge 58 Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
Page 71
Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009...
Page 72
Controls Group www.johnsoncontrols.com 507 E. Michigan Street P.O. Box 423 Release G Milwaukee, WI 53201 Printed in U.S.A.
Need help?
Do you have a question about the IFC-200 and is the answer not in the manual?
Questions and answers