Compressor control panel communications setup
Hide thumbs Also See for FRICK QUANTUM HD:
Table of Contents

Advertisement

Quick Links

COMMUNICATIONS SETUP
FRICK
QUANTUM™ HD
®
COMPRESSOR
CONTROL PANEL
Version 10.1x
Form 090.040-CS (JANUARY 2014)
COMUNICATIONS SETUP
File:
SERVICE MANUAL - Section 90
Replaces:
090.040-CS DECEMBER 2013
Dist:
3, 3a, 3b, 3c

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the FRICK QUANTUM HD and is the answer not in the manual?

Questions and answers

Summary of Contents for Johnson Controls FRICK QUANTUM HD

  • Page 1 Form 090.040-CS (JANUARY 2014) COMUNICATIONS SETUP File: SERVICE MANUAL - Section 90 Replaces: 090.040-CS DECEMBER 2013 Dist: 3, 3a, 3b, 3c COMMUNICATIONS SETUP FRICK QUANTUM™ HD ® COMPRESSOR CONTROL PANEL Version 10.1x...
  • Page 2: Table Of Contents

    090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 2 COMMUNICATIONS SETUP TABLE OF CONTENTS SECTION 1 INTRODUCTION TO THE QUANTUM™ HD..........................5 Quantum™ HD Description................................6 How To Use This Manual................................6 ETHERNET AND NETWORKING............................7 Description....................................7 Cabling......................................7 RJ-45 Connectors ..................................8 The Hub....................................8 The Switch....................................8 Ethernet Setup..................................10 SECTION 2...
  • Page 3 QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 3 Data Field....................................46 Error Checking..................................46 ASCII....................................46 RTU....................................46 Framing....................................46 ASCII....................................47 RTU....................................47 ASCII Query (Read) Example............................48 ASCII Write Example..............................49 ASCII Response Example............................51 RTU Query (Read) Example............................52 RTU Response Example............................52 Modbus® Notes................................52 Modbus®...
  • Page 4 Any modification to the standard default settings may have a severe negative impact on the operation and performance of the equipment. Any modification to these control settings is the sole responsibility of the user/owner and Johnson Controls disclaims any liability for the consequences of these modifications. It is possible that the modification of these settings may cause improper...
  • Page 5: Introduction To The Quantum™ Hd

    QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 5 SECTION 1 INTRODUCTION TO THE QUANTUM™ HD CONTROL SYSTEM...
  • Page 6: Quantum™ Hd Description

    090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 6 COMMUNICATIONS SETUP operation and performance that result in property damage, allows for data accessing and viewing. personal injury or death. It is the responsibility of the user/ owner to evaluate and assess the consequences of their ac- The Quantum™...
  • Page 7: Ethernet And Networking

    QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 7 tion 8 for the correct wiring and jumper settings of Quantum™ HD to do this behind the scenes work, so RS-422, or RS-485. that it can communicate both at the Internet level, and at a local Ethernet level.
  • Page 8: Rj-45 Connectors

    090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 8 COMMUNICATIONS SETUP • Label the ends of each cable, to facili- see all packets. tate troubleshooting and identifying in the future. THE SWITCH • Test each individual cable run with an approved CAT5 E cable tester.
  • Page 9 QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 9 Switch. Both Ends of a crossover-cable CAT-5 Ethernet cable color codes Refer to the following pictorial to construct a crossover cable: 1 – White w/orange stripe 5 – White w/blue stripe 2 –...
  • Page 10: Ethernet Setup

    090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 10 COMMUNICATIONS SETUP ** UTP = Unshielded Twisted Pair Once all of the cabling has been run and all connections ETHERNET SETUP have been made, the next step is to setup the Quantum™ HD software for connecting the panel to an existing Eth- CONFIGURATION Communications - Ethernet...
  • Page 11: Serial Communications

    QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 11 SECTION 2 SERIAL COMMUNICATIONS • Enabled time. It cannot do both at the same time. Frick ® SERIAL COMMUNICATIONS DESCRIPTION Controls uses a 2-wire system for RS-485 one positive transmit/receive wire and one negative transmit/receive wire).
  • Page 12: Serial Communications Setup

    090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 12 COMMUNICATIONS SETUP CONFIGURATION Communications - Serial ACCESSING: Communications Serial DESCRIPTION: This screen is used to set the Serial communi- pop-up menu is provided to select from the follow- cations parameters for Comm1, Comm2 and Comm 3. ing: NOTE: Comm1 and Comm2 may be either RS422 or RS485, •...
  • Page 13 QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 13 tion in communications. A pop-up menu is provided: An additional button is provided to allow the user to set the Panel ID for this unit: • None • Even [Panel ID] - A number that is used by an external •...
  • Page 14: Creating And Using The Map File

    090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 14 COMMUNICATIONS SETUP CONFIGURATION Communications - Map File ACCESSING: Communications Map File DESCRIPTION: This screen allows the user to upload a pre- want to utilize the same code for the viously created serial communications application that was originally done for the Quantum™...
  • Page 15 QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 15 As an example, assume that you have an existing dress conversion to the Quantum™ HD per the in- communications monitoring application that was structions provided on the previous page. written around the Quantum™...
  • Page 16: Serial Communication Setup Table

    090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 16 COMMUNICATIONS SETUP ERIAL COMMUNICATION SETUP TABLE Use the following form to record all settings: Compressor ID _______ (0 - 255) Com 1 (RS-422/485) Com 2 (RS-422/485) Com 3 (RS-485)  1200 ...
  • Page 17: Serial Protocol

    QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 17 SERIAL PROTOCOL identify commands that are sent to it. Wire to the first panel via RS-422, or RS-485 to DESCRIPTION the Quantum™ HD Comm Port. The use of serial communication protocols permits Send a single command to read data from this data transmission between devices.
  • Page 18: Frick ® Protocol

    090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 18 COMMUNICATIONS SETUP FRICK PROTOCOL The following is a complete list of available Frick® Proto- ® col # commands: DESCRIPTION COMMAND CODE and DESCRIPTION = Returns compressor status (I)nformation All commands for Frick® protocols must be in ASCII to be recognized (see the Conversion Chart = Compressor sta(R)t control For Decimal / Hexadecimal / ASCII, located later...
  • Page 19 QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 19 The following is a detailed description of each command: Note: The following control commands are for remote con- trol of a compressor. A compressor should be in both remote compressor mode and remote Slide Valve or capacity mode RETURN COMPRESSOR STATUS INFO: #IDI...
  • Page 20 090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 20 COMMUNICATIONS SETUP RETURN FULL LOAD AMPS COMMAND: #IDA RETURN SLIDE STOP POSITION COMMAND: #IDVP Command structure: Command structure: Command Description Command Description Start command sequence Start command sequence Compressor (ID) code (01, 14, etc.) Compressor (ID) code (01, 14, etc.) Return Full Load (A)mps command Slide (V)alve / Slide Stop command...
  • Page 21 QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 21 CHANGE SLIDE VALVE MODE #IDMVmID RETURN TEMPERATURES COMMAND: #IDTX COMMAND: Command structure: Command structure: Command Description Command Description Start command sequence Start command sequence Compressor (ID) code (01, 14, etc.) Compressor (ID) code (01, 14, etc.) Return (T)emperature command (M)ode of Compressor Slide (V)alve...
  • Page 22 090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 22 COMMUNICATIONS SETUP QUERY SETPOINTS DATA: #IDQ1 QUERY SETPOINTS DATA: #IDQ2 Command structure: Command structure: Command Description Command Description Start command sequence Start command sequence Compressor (ID) code (01, 14, etc.) Compressor (ID) code (01, 14, etc.) (Q)uery Setpoints command (Q)uery Setpoints command...
  • Page 23 QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 23 QUERY SETPOINTS DATA: #IDQ3 CHANGE SETPOINTS COMMAND: #IDC Command structure: Command structure: Command Description Command Description Start command sequence Start command sequence Compressor (ID) code (01, 14, etc.) Compressor (ID) code (01, 14, etc.) (C)hange setpoint command (Q)uery Setpoints command...
  • Page 24 090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 24 COMMUNICATIONS SETUP RETURN FAILURE COMMAND: #IDF CLEAR FAILURE COMMAND: #IDKFID Command structure: Command structure: Command Description Command Description Start command sequence Start command sequence Compressor (ID) code (01, 14, etc.) Compressor (ID) code (01, 14, etc.) Return Discrete (F)ailures List (K)Clear (F)ailures...
  • Page 25: Quantum™ $ Protocol Specifications

    QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 25 QUANTUM™ $ PROTOCOL SPECIFICATIONS $01T1. Now you to need specify the address(s) that you wish to query. Up to sixteen addresses may simultane- Quantum™ ($) protocol commands are used by both the ously be requested.
  • Page 26 090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 26 COMMUNICATIONS SETUP sponse. The format of this response should resemble CLEAR ALARMS COMMAND: $IDCA something (but not necessarily exactly) like: Command structure: A01+00006166B6 Command Description Referring to the RETURN DATA VALUE FROM TABLE $IDT1 Start command sequence table on the next page, we find that the first line of the Compressor (ID) code (01, 14, etc.)
  • Page 27 QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 27 COMPRESSOR STOP COMMAND: $IDCP COMPRESSOR START COMMAND: $IDCT Command structure: Command structure: Command Description Command Description Start command sequence Start command sequence Compressor (ID) code (01, 14, etc.) Compressor (ID) code (01, 14, etc.) (C)ompressor (S)top (C)ompressor S(T)art...
  • Page 28 090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 28 COMMUNICATIONS SETUP RETURN OPERATING STATUS – RETURN OPERATING STATUS – $IDD1 $IDD2 Page 1 Data: Page 2 Data: Command structure: Command structure: Command Description Command Description Start of command sequence. Start of command sequence.
  • Page 29 QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 29 RETURN OPERATING STATUS – RETURN Alarms & Shutdowns – $IDD3 $IDF1 Page 3 Data: Page 1 Data: Command structure: Command Description Command structure: Start of command sequence Command Description Compressor (ID) code (01, 14, etc.) Start of command sequence Operating Status (D)ata –...
  • Page 30 090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 30 COMMUNICATIONS SETUP RETURN Alarms & Shut- RETURN Alarms & Shutdowns – $IDF2 downs – $IDF3 Page 2 Data: Page 3 Data: Command structure: Command structure: Command Description Command Description Start of command sequence Start of command sequence.
  • Page 31 QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 31 NOTE: The following commands are for remote control of a RETURN Data Value From Table: $IDT1 compressor. A compressor should be in both remote compres- sor mode and remote Slide Valve or capacity mode for remote control.
  • Page 32 090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 32 COMMUNICATIONS SETUP COMPRESSOR MODE – SLIDE VALVE MODE – $IDMR $IDVA REMOTE COMMAND: AUTOMATIC COMMAND: Command structure: Command Description Command structure: Start of command sequence. Command Description Compressor (ID) code (01, 14, etc.) Start of command sequence.
  • Page 33: Quantum™ Hd Allen-Bradley Communication

    QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 33 SECTION 3 QUANTUM™ HD ALLEN-BRADLEY COMMUNICATION QUANTUM™ HD ALLEN-BRADLEY COMMUNICATION to Flash memory will interfere with the communica- tions to its I/O Boards. A communication failure to an I/O board will cause the compressor to shutdown. This section contains programming examples for reading Control commands such as starting the compressor data from and writing data to the Frick Quantum control...
  • Page 34: Slc-500 - Suggested Setup

    090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 34 COMMUNICATIONS SETUP allow the SLC Typed Logical Read/Write Message READ MESSAGE SETUP EXAMPLE Command. Read/Write Message Type: Peer-To-Peer SLC-500 - Suggested Setup Read/Write: Read Target Device: 500 CPU The following are representations of the channel Local/Remote: Local configuration screens from the AB RSLogix500 pro- Control Block: N11:0...
  • Page 35: Allen-Bradley Programming Overview

    QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 35 ALLEN-BRADLEY PROGRAMMING OVERVIEW CHANNEL CONFIGURATION The following are representations of the channel con- This section contains programming examples for reading figuration screens from the AB RSLogix500 program- data from, and writing data to the Frick® Quantum™ HD ming software for the SLC500.
  • Page 36: System Configuration

    090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 36 COMMUNICATIONS SETUP System Configuration sage to the Quantum™ HD panel. This logic prevents hang Message Sequence Logic up due to lost communications or message errors. Use the following logic to sequence read and write mes-...
  • Page 37: Message Read Logic

    QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 37 Message Read Logic Delay Between Messages Use the following logic to read data from the Quantum™ The delay timer on rung 3 must be used when commu- HD panel. To read more data or to read data from several nicating to the Quantum™...
  • Page 38: Message Read Setup Screen

    090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 38 COMMUNICATIONS SETUP MESSAGE READ SETUP SCREEN N10:1 register and place them into the SLC500’s N10:1 through N10:28 register. The target address must be The following setup screen is programmed to obtain 28 changed to for the Quantum™...
  • Page 39: Message Write Logic

    QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 39 executed when counter 5:0 (logic shown above) is equal Message Write Logic to 1 and when called upon by the change compressor Use the following logic to write data from the Quantum™ mode bit B3/2.
  • Page 40 090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 40 COMMUNICATIONS SETUP - Continued from previous page -...
  • Page 41: Message Write Setup Screen

    QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 41 MESSAGE WRITE SETUP SCREEN N55:3 data file from the SLC500’s N55:3 data file. The target address must be changed to for the Quan- tum™ HD. The following setup screen is programmed to write the compressor mode to the Quantum™...
  • Page 42 090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 42 COMMUNICATIONS SETUP NOTES:...
  • Page 43: Modbus® Protocol

    QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 43 SECTION 4 MODBUS PROTOCOL ® MODBUS® Protocol The address references are numbered relative to the Frick® addresses in the Quantum™ Data Table (see MODBUS Addressing Note in the Quantum™ Data General Description Table section of this manual for additional informa- tion).
  • Page 44 090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 44 COMMUNICATIONS SETUP STATUS Panel - ModBus TCP Log Panel ModBus TCP Log ACCESSING: DESCRIPTION: This screen allows the technician to view all of ceive or Send), and the actual data (in Hexadecimal format). the Modbus TCP communications information that the Quan- This information can be used to compare against the data be- tum™...
  • Page 45: Modbus® Ascii (Serial Communications)

    QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 45 MODBUS® ASCII (Serial Communications) ed action (Query): • Function Code 3 - to read holding regis- In the ASCII Transmission Mode (American Standard ters (sends a request to read data from the Code for Information Interchange), each character Quantum™).
  • Page 46: Error Checking

    090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 46 COMMUNICATIONS SETUP The data field of messages sent from a leader to the The CRC field is two bytes, containing a 16–bit Quantum™ devices contains additional information binary value. The CRC value is calculated by the which the Quantum™...
  • Page 47: Ascii

    QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 47 addressed device. A MODBUS® message is placed by the In RTU mode, messages start with a silent transmitting device into a frame that has a interval of at least 3.5 character times. This known beginning and ending point.
  • Page 48: Ascii Query (Read) Example

    090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 48 COMMUNICATIONS SETUP ASCII Query (Read) Example To demonstrate how an address within the Quan- : 01 06 1B EE 03 E8 05 CRLF tum™ may be read, the following test can be per- Where: formed using Windows HyperTerminal (NOTE: Hyper- Message Start:...
  • Page 49: Ascii Write Example

    QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 49 so our decimal 1 is formatted as 0001 (hex). As an example, a MODBUS® command will be cre- ated and sent to the Quantum™ to set Regulation Mode 1 Setpoint to 100.0 PSIA. First, be aware that : 01 03 07 D3 00 01 21 CRLF data sent to and received by the Quantum™...
  • Page 50 090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 50 COMMUNICATIONS SETUP : 01 06 1B EE 03 E8 05 CRLF : 01 06 1B EE 03 E8 05 CRLF Where: Where: Message Start: Message Start: Quantum™ ID #: Quantum™ ID #: Write Function: Write Function: H.
  • Page 51: Ascii Response Example

    QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 51 ASCII Response Example If the packet was properly received by the Quan- : 01 03 02 05 D0 25 tum™, you should see an immediate response in Hy- Where: perTerminal.
  • Page 52: Rtu Query (Read) Example

    090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 52 COMMUNICATIONS SETUP you may need to compensate. # OF STARTING START ADD. FUNC. REGISTERS • 7 or 8 bits selectable. ADDRESS CHECK TO LOAD • 1 or 2 Stop bits selectable. T1-T2-T3-T4 * T1-T2-T3-T4 •...
  • Page 53: Hyperterminal

    QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 53 SECTION 5 HYPERTERMINAL important, and that function is not affected by the DESCRIPTION HyperTerminal is a terminal emulation pro- way the screen looks. gram which resides in the Microsoft Windows environment, and as such, will normally be found on any computer that is •...
  • Page 54 090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 54 COMMUNICATIONS SETUP normally would need to be changed from one protocol to the next is the Data Bits box. For the purpose of this document, Frick # protocol will be ®...
  • Page 55: Testing Communications

    QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 55 tum™ with ID 01 to send a packet of Information.) The Properties screen will once again be shown. Click on the [OK] button to proceed. If the communications is working properly, there should be an immediate response from the first Quantum™.
  • Page 56 090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 56 COMMUNICATIONS SETUP would be best to consult the HyperTerminal section of this manual for more detailed troubleshooting. If no data appears, or if the data does not match the spe- cific protocol requirements that you are using, then check the following: •...
  • Page 57: Conversion Chart For Decimal / Hexadecimal / Ascii

    QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 57 CONVERSION CHART FOR DECIMAL / HEXADECIMAL / ASCII Decimal Hexadecimal Decimal Hexadecimal Decimal Hexadecimal ASCII ASCII ASCII (DEC) (HEX) (DEC) (HEX) (DEC) (HEX) ctrl @ NUL ctrl A SOH ctrl B STX ctrl C ETX ctrl D EOT...
  • Page 58 090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 58 COMMUNICATIONS SETUP NOTES:...
  • Page 59: Quantum™ Hd Data Tables

    QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 59 SECTION 6 QUANTUM™ HD DATA TABLES The following table shows the three protocol Address ranges that may be utilized for reading/writing data to and from the Quantum™ HD controller; Frick Addresses, Allen-Bradley (AB) Addresses, and Modbus Addresses.
  • Page 60: Digital Board Values

    090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 60 COMMUNICATIONS SETUP DIGITAL BOARD VALUES: (Read Only) Frick Modbus Digital Channel Module ® Read/Write Description of Data Address Address Address Board # Type 1001 N10:1 41002 Oil Level/Oil Switch Input 1002 N10:2 41003...
  • Page 61 QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 61 DIGITAL BOARD VALUES: (Read Only, Continued) Frick ® Modbus Digital Channel Module Read/Write Description of Data Address Address Address Board # Type 1063 N10:63 41064 User Defined Digital Input #1 1064 N10:64 41065...
  • Page 62: Analog Board Values

    090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 62 COMMUNICATIONS SETUP ANALOG BOARD VALUES: Frick ® Modbus Analog Channel Module Read/Write Description of Data Address Address Address Board # Type 2001 N20:1 42002 Volume Slide Position 2002 N20:2 42003 Suction Pressure 2003 N20:3...
  • Page 63 QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 63 ANALOG BOARD VALUES: (Continued) Frick Modbus Analog Channel Module ® Read/Write Description of Data Address Address Address Board # Type 2059 N20:59 42060 Analog Output #1 2060 N20:60 42061 Analog Output #2 None...
  • Page 64: Calculated Values

    090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 64 COMMUNICATIONS SETUP CALCULATED VALUES: Frick Modbus ® Read/Write Description of Data Units Address Address Address 3000 N30:0 43001 Calculated Capacity Percent (%) 3006 N30:6 43007 Filter Differential Pressure Pressure (Magnitude) 3008 N30:8 43009...
  • Page 65: Mode Values

    QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 65 CALCULATED VALUES: (Continued) Frick Modbus ® Read/Write Description of Data Units Address Address Address 3102 N31:02 43103 Coalescer Filter Differential Pressure (Magnitude) 3103 N31:03 43104 Calculated Superheat 1 Temperature (Magnitude) 3104 N31:04...
  • Page 66 090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 66 COMMUNICATIONS SETUP MODE VALUES: (Continued) Frick Modbus Read/ ® Description of Data Value Code Address Address Address Write 0 = Not In Recycle Delay 4006 N40:6 44007 Recycle Delay Time 1 = In Recycle Delay 0 = Manual 1 = Automatic...
  • Page 67 QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 67 MODE VALUES: (Continued) Frick Modbus Read/ ® Description of Data Value Code Address Address Address Write 0 = None 1 = Inhibit-Motor Current 2 = Inhibit-Low Suction Regulation 1 3 = Inhibit-Low Suction Regulation 2 4 = Inhibit-Low Suction Regulation 3 5 = Inhibit-Low Suction Regulation 4...
  • Page 68 090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 68 COMMUNICATIONS SETUP MODE VALUES: (Continued) Frick Modbus Read/ ® Description of Data Value Code Address Address Address Write 0 = Disabled 4027 N40:27 44028 Condenser Enabled 1 = Running 2 = Always 0 = Ready 1 = Start Inhibit In Shutdown 2 = Start Inhibit In Recycle Delay...
  • Page 69 QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 69 MODE VALUES: (Continued) Frick ® Modbus Read/ Description of Data Value Code Address Address Address Write -1 = Idle 4201 N42:01 44202 Manual Compressor Action 0 = Stop 1 = Run 1 = R11 14 = R22...
  • Page 70 090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 70 COMMUNICATIONS SETUP MODE VALUES: (Continued) Frick ® Modbus Read/ Description of Data Value Code Address Address Address Write 4383 N43:83 44384 Sequencing – Sys. 1 Comp 1 Comp Mode 4384 N43:84 44385 Sequencing –...
  • Page 71 QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 71 MODE VALUES: (Continued) Frick Modbus Read/ ® Description of Data Value Code Address Address Address Write 0 = Disabled 4457 N44:57 44458 Sequencing Enable - System 2 1 = Enabled 4467 N44:67 44468...
  • Page 72 090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 72 COMMUNICATIONS SETUP MODE VALUES: (Continued) Frick ® Modbus Read/ Description of Data Value Code Address Address Address Write 0 = Disabled 4534 N45:34 44535 Screen Saver 1 = Enabled 4539 N45:39 44540 Starter Alarms...
  • Page 73: Timer Values

    QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 73 TIMER VALUES: (Read Only) Frick Modbus Read/ ® Description of Data Address Address Address Write 6000 N60:00 46001 Pre-Lube Timer 6001 N60:01 46002 Post-lube Timer 6002 N60:02 46003 Stopping Unload Timer 6003 N60:03...
  • Page 74: Setpoint Values

    090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 74 COMMUNICATIONS SETUP SETPOINT VALUES: Frick ® Modbus Read/ Description of Data Units Address Address Address Write 7060 N100:60 47061 Screen Saver Delay Setpoint Minutes 7061 N100:61 47062 Atmospheric Pressure Pressure (Magnitude) 7100 N101:00 47101...
  • Page 75 QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 75 SETPOINT VALUES (Continued): Frick ® Modbus Read/ Description of Data Units Address Address Address Write 7204 N102:04 47205 Regulation Mode 2 High Proportional Band Temperature (Magnitude) 7205 N102:05 47206 Regulation Mode 2 Low Proportional Band 7206...
  • Page 76 090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 76 COMMUNICATIONS SETUP SETPOINT VALUES (Continued): Frick ® Modbus Read/ Description of Data Units Address Address Address Write 7273 N102:73 47274 Low Suction Pressure Mode 3 Force Unload 7276 N102:76 47277 Mode 3 Prop Band Pressure 7277...
  • Page 77 QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 77 SETPOINT VALUES (Continued): Frick Modbus Read/ ® Description of Data Units Address Address Address Write 7364 N103:64 47365 Horsepower Integer 7365 N103:65 47366 Recycle Delay Minutes 7366 N103:66 47367 CT Factor None...
  • Page 78 090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 78 COMMUNICATIONS SETUP SETPOINT VALUES (Continued): Frick ® Modbus Read/ Description of Data Units Address Address Address Write 7415 N104:15 47416 Volume Middle Real 7416 N104:16 47417 Volume Deadband 7417 N104:17 47418 Volume Pulse Time 7418...
  • Page 79 QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 79 SETPOINT VALUES (Continued): Frick ® Modbus Read/ Description of Data Units Address Address Address Write 7464 N104:64 47465 Time Schedule Thursday 4th Mode Minute 2 7465 N104:65 47466 Time Schedule Friday 1st Mode Hour 1 7466 N104:66...
  • Page 80 090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 80 COMMUNICATIONS SETUP SETPOINT VALUES (Continued): Frick ® Modbus Read/ Description of Data Units Address Address Address Write 7529 N105:29 47530 High Discharge Pressure Shutdown Mode 1 Pressure (Positive) 7530 N105:30 47531 High Discharge Pressure Warning Mode 1 Delay Seconds...
  • Page 81 QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 81 SETPOINT VALUES (Continued): Frick Modbus Read/ ® Description of Data Units Address Address Address Write 7582 N105:82 47583 Low Separator Temperature Shutdown Delay 7583 N105:83 47584 Low Separator Temperature Warning Delay 7584 N105:84 47585...
  • Page 82 090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 82 COMMUNICATIONS SETUP SETPOINT VALUES (Continued): Frick ® Modbus Read/ Description of Data Units Address Address Address Write 7661 N106:61 47662 Dx Circuit 1Off When Below 7662 N106:62 47663 Dx Circuit 2 On When Above Percent (%) 7663 N106:63...
  • Page 83 QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 83 SETPOINT VALUES (Continued): Frick Modbus Read/ ® Description of Data Units Address Address Address Write 7715 N107:15 47716 Auxiliary Input 16 Delay 7716 N107:16 47717 Auxiliary Input 17 Delay 7717 N107:17 47718...
  • Page 84 090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 84 COMMUNICATIONS SETUP SETPOINT VALUES (Continued): Frick ® Modbus Read/ Description of Data Units Address Address Address Write 7772 N107:72 47773 Auxiliary Analog 5 High Warning Pressure 7773 N107:73 47774 Auxiliary Analog 5 High Warning Delay Seconds 7774 N107:74...
  • Page 85 QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 85 SETPOINT VALUES (Continued): Frick ® Modbus Read/ Description of Data Units Address Address Address Write 7822 N108:22 47823 Auxiliary Analog 10 High Warning Pressure 7823 N108:23 47824 Auxiliary Analog 10 High Warning Delay Seconds 7824 N108:24...
  • Page 86 090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 86 COMMUNICATIONS SETUP SETPOINT VALUES (Continued): Frick ® Modbus Read/ Description of Data Units Address Address Address Write 7873 N108:73 47874 Auxiliary Analog 15 High Warning Delay Seconds 7874 N108:74 47875 Auxiliary Analog 15 Low Shutdown Pressure 7875...
  • Page 87 QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 87 SETPOINT VALUES (Continued): Frick ® Modbus Read/ Description of Data Units Address Address Address Write 7921 N109:21 47922 Auxiliary Analog 20 High Shutdown Delay Seconds 7922 N109:22 47923 Auxiliary Analog 20 High Warning Pressure 7923...
  • Page 88 090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 88 COMMUNICATIONS SETUP SETPOINT VALUES (Continued): Frick Modbus Read/ ® Description of Data Units Address Address Address Write 8024 N110:24 48025 PID 4 Setpoint 8025 N110:25 48026 PID 4 Deadband None 8026 N110:26 48027...
  • Page 89 QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 89 SETPOINT VALUES (Continued): Frick Modbus Read/ ® Description of Data Units Address Address Address Write 8072 N110:72 48073 High Compressor Vibration Warning - Discharge Vibration (Fg) 8073 N110:73 48074 High Compressor Vibration Warning Delay - Discharge Seconds...
  • Page 90 090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 90 COMMUNICATIONS SETUP SETPOINT VALUES (Continued): Frick Modbus Read/ ® Description of Data Units Address Address Address Write 8204 N112:04 48205 Clean Liquid Strainers Service Interval 8205 N112:05 48206 Clean Coalescers Service Interval 8206 N112:06 48207...
  • Page 91 QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 91 SETPOINT VALUES (Continued): Frick Modbus Read/ ® Description of Data Units Address Address Address Write 8311 N113:11 48312 Sequencing - System 1 Compressor 4 Start # 8312 N113:12 48313 Sequencing - System 1 Compressor 5 Start # 8313...
  • Page 92 090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 92 COMMUNICATIONS SETUP SETPOINT VALUES (Continued): Frick Modbus Read/ ® Description of Data Units Address Address Address Write 8354 N113:54 48355 Sequencing - System 1 Compressor 4 Start Inhibits 8355 N113:55 48356 Sequencing - System 1 Compressor 5 Start Inhibits 8356...
  • Page 93 QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 93 SETPOINT VALUES (Continued): Frick Modbus Read/ ® Description of Data Units Address Address Address Write 8435 N114:35 48436 Sequencing - System 2 Compressor 1 Minimum Capacity 8436 N114:36 48437 Sequencing - System 2 Compressor 2 Minimum Capacity 8437...
  • Page 94 090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 94 COMMUNICATIONS SETUP SETPOINT VALUES (Continued): Frick ® Modbus Read/ Description of Data Units Address Address Address Write 8518 N115:18 48519 Sequencing - System 3 Minimum Run Time Minutes 8519 N115:19 48520 Sequencing - System 3 Compressor 1 Capacity 8520...
  • Page 95: Commands

    QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 95 COMMANDS: Frick® Modbus Read/ Description of Data Value Codes Address Address Address Write 8910 N119:10 48911 Remote – Start 1 = Start 8911 N119:11 48912 Remote – Stop 1 = Stop 0 = Turn off See Note 1...
  • Page 96: Dbs Setpoint Values

    090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 96 COMMUNICATIONS SETUP DBS SETPOINT VALUES: Frick Modbus Read/ ® Description of Data Units Address Address Address Write 8950 N119:50 48951 Average Current Amps 8951 N119:51 48952 Elapsed Run Time Hours Hours 8952 N119:52...
  • Page 97: General Setpoint Values

    QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 97 DBS SETPOINT VALUES (Continued): Frick Modbus Read/ ® Description of Data Units Address Address Address Write 8998 N119:98 48999 Stall Time Setpoint Seconds 8999 N119:99 49000 Jam Current Level Setpoint Percent (%) 9000 N120:00...
  • Page 98 090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 98 COMMUNICATIONS SETUP VSD (VYPER) SETPOINT VALUES (Continued): Frick Modbus Read/ ® Description of Data Units Address Address Address Write 9231 N122:31 49232 Vyper Drive Job FLA 9232 N122:32 49233 Vyper Drive DC Inverter Link Current 9233 N122:33 49234...
  • Page 99 QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 99 VSD (VYPER) SETPOINT VALUES (Continued): Frick Modbus Read/ ® Description of Data Units Address Address Address Write 9276 N122:76 49277 Vyper Drive Run Acknowledge Relay Status 9277 N122:77 49278 Vyper Drive Run Command Relay Status 9278...
  • Page 100 090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 100 COMMUNICATIONS SETUP NOTES:...
  • Page 101: Warning/Shutdown Message Codes

    QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 101 SECTION 7 WARNING/SHUTDOWN MESSAGE CODES The following list represents all of the current warning/shut- Low Suction Warning - Regulation Mode 4 down messages that are potentially displayable (at the time of Regulation Mode 1 Shutdown this writing).
  • Page 102 090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 102 COMMUNICATIONS SETUP WARNING/SHUTDOWN MESSAGE CODES (Continued) Auxiliary Input 6 Warning Low Auxiliary Analog 9 Warning Auxiliary Input 7 Shutdown High Auxiliary Analog 10 Shutdown Auxiliary Input 7 Warning High Auxiliary Analog 10 Warning Auxiliary Input 8 Shutdown Low Auxiliary Analog 10 Shutdown Auxiliary Input 8 Warning...
  • Page 103 QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 103 WARNING/SHUTDOWN MESSAGE CODES (Continued) Low Auxiliary Analog 13 Warning Oil Pump 2 Auxiliary Shutdown High Auxiliary Analog 14 Shutdown Low Comp. Oil Pressure Warning High Auxiliary Analog 14 Warning Low Comp.
  • Page 104 090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 104 COMMUNICATIONS SETUP WARNING/SHUTDOWN MESSAGE CODES (Continued) VSD High DC Bus Voltage Fault Low Process Entering Temp Warning VSD Logic Board Power Supply Fault High Motor Temp Warning - Shaft Side VSD Low DC Bus Voltage Fault High Motor Temp Warning - Opp Shaft Side VSD DC Bus Voltage Imbalance Fault...
  • Page 105 QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 105 WARNING/SHUTDOWN MESSAGE CODES (Continued) High Auxiliary Analog Input #8 Sensor Warning High Process Leaving Temp Sensor Warning Low Auxiliary Analog Input #9 Sensor Warning Low Process Entering Temp Sensor Warning High Auxiliary Analog Input #9 Sensor Warning High Process Entering Temp Sensor Warning Low Auxiliary Analog Input #10 Sensor Warning...
  • Page 106 090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 106 COMMUNICATIONS SETUP NOTES:...
  • Page 107: Q5 Controller

    QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 107 SECTION 8 Q5 CONTROLLER AND INTERFACE...
  • Page 108: Main Board History And Identification

    090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 108 COMMUNICATIONS SETUP Q5 CONTROLLER MAIN BOARD HISTORY AND IDENTIFICATION The Q5 utilizes Flash Card technology. There is a Flash Card socket located on the under side of this main board. The Q5 board has the HD Operating System pre-loaded The processor board shown on this page is known as the at the factory, and the card must be present for the HD...
  • Page 109: Serial Communications Hardware

    QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 109 Q5 SERIAL COMMUNICATIONS HARDWARE COM-1 AND COM-2 DESCRIPTION The board pictured on this page has two RS-422/485 se- Q5 GENERAL DESCRIPTION rial communications ports, labeled P10 (Com-1) and P11 (Com-2).
  • Page 110: Serial Communications Port Wiring

    090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 110 COMMUNICATIONS SETUP Q5 SERIAL COMMUNICATIONS PORT WIRING to the tables in this section for the specifics on the jumper settings RS-422/485: GENERAL NOTE RS-422/485 Connectors, Jumpers and LED Location The information that is presented here and on the following pages, refers to the Interface board and not the Q5 board.
  • Page 111: Q5 Interconnections

    QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 111 Q5 INTERCONNECTIONS The pictorial below depicts the Q5 motherboard, and the nec- essary interconnects between it and the Interface If the harness for either COMM1 or COMM2 is ever removed for either repair, replacement or troubleshooting, ensure...
  • Page 112: Serial Communications Troubleshooting

    090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 112 COMMUNICATIONS SETUP SERIAL COMMUNICATIONS TROUBLESHOOTING If communications cannot be established us- ing COMM-2, then note the status of these two LED’s (D25 and D26). If D25 is constantly lit, it WIRING NOTE: See the chapter entitled Serial Commu- may indicate an external wiring issue (TX and RX nications Port Wiring, for the pictorials and tables re-...
  • Page 113 QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 113 flash each time that data is received (RX). COMM-3 (P16) If communications cannot be established us- COMM-3 may only be used for RS-485. There are ing COMM-2, then note the status of these two no jumpers or LED’s assoiciated with this port.
  • Page 114 090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 114 COMMUNICATIONS SETUP NOTES:...
  • Page 115: Communications Setup

    QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 115 SECTION 9 APPENDICES APPENDIX A FRICK SERIAL COMMUNICATIONS CONVERTER MODULE ® (Part Number 639B0086H01) DESCRIPTION of each end. Hold the module as shown in the following pictorial: Frick ®...
  • Page 116: Mounting The Module

    090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 116 COMMUNICATIONS SETUP For easy reference, the DIP switch position functions are WIRING THE MODULE provided on the board. For the purpose of clarity however, refer to the following table: There are twelve total wire terminal points on this mod- ule.
  • Page 117: Rs-422 Connections

    QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 117 RS-422 CONNECTIONS RS-485 CONNECTIONS Refer to the following figure for the pin connections Although typical RS-485 communications requires a con- showing how to attach a 4-wire RS-422 cable directly to trol signal to change the state of the RX/TX driver lines the Frick ®...
  • Page 118 090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 118 COMMUNICATIONS SETUP...
  • Page 119: Quantum™ Hd Ethernet Communications Wiring

    QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 119 APPENDIX B QUANTUM™ HD ETHERNET COMMUNICATIONS WIRING...
  • Page 120: Quantum™ Hd Local Ethernet Configurations

    090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 120 COMMUNICATIONS SETUP APPENDIX C QUANTUM™ HD LOCAL ETHERNET CONFIGURATIONS Switch Computer Quantum™ HD Quantum™ HD...
  • Page 121: Quantum™ Hd Serial Communications Wiring

    QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 121 APPENDIX D QUANTUM™ HD SERIAL COMMUNICATIONS WIRING...
  • Page 122: Serial Connections Pictorial

    090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 122 COMMUNICATIONS SETUP SERIAL CONNECTIONS PICTORIAL...
  • Page 123: To Customer Remote Computer/Dcs

    QUANTUM™ HD COMPRESSOR CONTROL PANEL 090.040-CS (JAN 14) COMMUNICATIONS SETUP Page 123 COMMUNICATIONS WIRING DIAGRAMS TO CUSTOMER REMOTE COMPUTER/DCS RS-485 COMMUNICATIONS Q1 OR Q2 Q3 OR Q4 Q3 OR Q4 To Customer COM-2 (P12) COM-2 (TB2) COM-2 (TB2) COM-2 (P11) Remote -RX/-TX -RX/-TX...
  • Page 124 090.040-CS (JAN 14) QUANTUM™ HD COMPRESSOR CONTROL PANEL Page 124 COMMUNICATIONS SETUP...
  • Page 125 100 CV Avenue • P.O. Box 997 Supersedes: 090.040-CS (2012-03) Subject to change without notice Waynesboro, PA USA 17268-0997 Phone: 717-762-2121 • FAX: 717-762-8624 Printed In USA - GUI 1M .20 2014 Johnson Controls Inc. - ALL RIGHTS RESERVED www.johnsoncontrols.com...

Table of Contents